| 2011-11-14 15:01:42 | 2007 FBC W/2009 REVISIONS |
| | REBUILD AND ENCLOSE EXISTING OPEN PORCH |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SUBMIT TWO CURRENT COPIES OF PRODUCT APPROVALS FOR |
| | THE WINDOWS, STORM PANELS AND ROOFING MATERIAL AS |
| | REQUIRED BY DCA RULE 9N-3. |
| | |
| | 2) SUBMIT TWO CURRENT COPIES OF PRODUCT APPROVALS FOR |
| | THE EXTERIOR DOOR AS REQUIRED BY DCA RULE 9N-3. THE |
| | ONES THAT WERE SUBMITTED HAVE BEEN SUPERSEDED. |
| | |
| | 3) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| | THE PROJECT. CITY AMENDMENTS 106.3.3 |
| | |
| | 4) ON SHEET A-2 THE ROOF AND WALL COMPONENT AND |
| | CLADDING PRESSURES ARE TOO LOW FOR EXPOSURE CATEGORY C. |
| | SEE ASCE7-05 AND FBCR TABLES R301.2(2) & R301.2(3). |
| | PLEASE CORRECT. |
| | |
| | 5) THE DRYER IS REQUIRED TO BE VENTED TO THE OUTSIDE OF |
| | THE BUILDING PER FBCR M1502.1. |
| | |
| | 6) SPECIFY THE UNDER FLOOR INSULATION REQUIRED BY FBCR |
| | N1105.AB.1. |
| | |
| | 7) INDICATE ON THE PLANS HOW COMPLIANCE WITH FBC R408.1 |
| | FOR UNDER-FLOOR SPACE VENTILATION IS ACHIEVED. |
| | |
| | 8) INDICATE ON THE PLANS HOW COMPLIANCE WITH FBC R |
| | 408.4 FOR ACCESS TO UNDER-FLOOR SPACE IS ACHIEVED. |
| | |
| | 9) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE |
| | BATHROOM ADDITION AS REQUIRED BY FBCR N1100.03. |
| | |
| | 10) PLEASE SUBMIT A RESPONSE LETTER SPECIFYING HOW THE |
| | PLAN REVIEW COMMENTS HAVE BEEN ADDRESSED. |
| | |