| 2011-11-16 11:36:05 | 601 CLEARWATER PARK ROAD | | | PERMIT #11100408 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FIRE ALARM SYSTEM SHALL BE UL (OR EQUAL) CERTIFICATED | | | FOR CENTRAL STATION SERVICE BY FINAL FIRE INSPECTION. | | | | | | NEW SMOKE DETECTORS SHALL BE INSTALLED NEAR THE | | | EXISTING FIRE SHUTTER. SMOKE DETECTORS AND FIRE ALARM | | | SYSTEM SHALL DROP THE EXISTING FIRE SHUTTER. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OF A FIRE ALARM SYSTEM AND | | | ACCESS-CONTROLLED SECURITY SYSTEM. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|