| Date |
Text |
| 2011-10-25 11:47:49 | 601 CLEARWATER PARK ROAD |
| | PERMIT #11100408 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL |
| | COVER SHEET INDICATES THIS BUILDING IS PROTECTED BY AN |
| | AUTOMATIC SPRINKLER SYSTEM. CONFIRM SPRINKLER SYSTEM IS |
| | EXISTING. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | ALL INSIDE STAIRS SERVING AS A REQUIRED EXIT SHALL BE |
| | ENCLOSED AND SHALL NOT BE USED FOR ANY PURPOSE THAT MAY |
| | INTERFERE WITH EXITING. ELEVATORS SHALL NOT OPEN TO AN |
| | EXIT. |
| | |
| | EAST STAIR EXIT CAN DISCHARGE TO FIRST FLOOR IF |
| | BUILDING IS PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | EXISTING STAIR DETAILS NOT PROVIDED. CONFIRM HANDRAILS |
| | ARE INSTALLED ON BOTH SIDES OF THE STAIR. HANDRAILS |
| | SHALL BE LOCATED NOT LESS THAN 34 INCHES AND NOT MORE |
| | THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD, MEASURED |
| | VERTICALLY TO THE TOP OF THE RAIL FROM THE LEADING EDGE |
| | OF THE TREAD. HANDRAIL ENDS SHALL BE RETURNED TO THE |
| | WALL OR FLOOR OR SHALL TERMINATE AT NEWEL POSTS. |
| | HANDRAIL CROSS SECTION SHALL HAVE A DIAMETER OF NOT |
| | LESS THAN 1.25 INCHES AND NOT MORE THAN 2 INCHES. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | CONFIRM THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN |
| | THE DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. |
| | THE RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF |
| | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF |
| | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE |
| | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST |
| | TO OPERATE. |
| | |
| | ELECTRICAL |
| | NO LIGHTING IN STAIR PROVIDED. |
| | |
| | NO EMERGENCY LIGHTING PROVIDED. |
| | |
| | PER LOCAL POLICY, DUCT SMOKE DETECTORS SHALL INITIATE A |
| | GENERAL FIRE ALARM CONDITION IN LIEU OF A TROUBLE |
| | SIGNAL. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |