| Plan Review Notes For Permit 11100388 |
| Permit Number |
11100388 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-11-16 14:38:53 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE NEW | | | ADDITION, AS REQUIRED BY FBCR N1100.0.3. THE FORMS ARE | | | REQUIRED TO BE SIGNED BY THE PREPARER AND THE | | | OWNER/AGENT. | | | | | | 2) THE NOAS THAT WERE SUBMITTED FOR THE WINDOWS HAVE | | | BEEN SUPERSEDED. SUBMIT TWO COPIES OF CURRENT PRODUCT | | | APPROVALS FOR THE LARGE MISSILE IMPACT RATED SINGLE | | | HUNG WINDOWS, AS REQUIRED BY DCA RULE 9N-3. | | | | | | 3) THE NOAS THAT WERE SUBMITTED FOR THE OUT-SWING | | | GLAZED ALUMINUM DOORS ARE RATED FOR SMALL MISSILE | | | IMPACT, HOWEVER, FBC R301.2.1.2 REQUIRES LARGE MISSILE | | | IMPACT PROTECTION FOR GLAZING UP TO 30 FEET ABOVE | | | GRADE. SUBMIT TWO COPIES OF CURRENT PRODUCT APPROVALS | | | FOR THE LARGE MISSILE IMPACT RATED DOORS OR STORM | | | PANELS, AS REQUIRED BY DCA RULE 9N-3. | | | | | | 4) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE | | | PROJECT. CITY AMENDMENTS 106.3.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|