Plan Review Notes
Plan Review Notes For Permit 11100384
Permit Number 11100384
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-10-25 10:16:332021 PALM BEACH LAKES BOULEVARD
 PERMIT #11100384
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL STORAGE ROOMS SHALL BE PROTECTED WITH A 1-HOUR
 FIRE RATED ENCLOSURE OR AUTOMATIC FIRE SPRINKLERS PER
 LIFE SAFETY CODE SECTION 37.3.2 AND SECTION 8.7 OF NFPA
 101 WITH FLORIDA AMENDMENTS.
  
 EXIT ACCESS IN CLASS B MERCATILE OCCUPANCIES IS
 PERMITTED TO PASS THROUGH STOREROOMS PROVIDED THE
 STOREROOM DOOR IS NOT SUBJECT TO LOCKING AND A 44-INCH
 WIDE AISLE IS PROVIDED FROM THE ROOM ENTRANCE DOOR TO
 THE EXIT DOOR. THE AISLE SHALL BE IDENTIFIED WITH FIXED
 BARRIERS TO MAINTAIN AN UNOBSTRUCTED EGRESS PATH.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  