2011-12-06 10:29:00FLAT ROOF BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- FLAT ROOF RAS 117 CALCULATIONS SUBMITTED:
  
 A) DESIGN PRESSURES SHOWN ARE A LITTLE BIT LOW FOR
 EXPOSURE "C". PLEASE PROVIDE ACTUAL CALCULATIONS TO
 SHOW HOW THE DESIGN PRESSURES WERE OBTAINED. SEC.
 106.1.2 CITY AMENDMENTS TO FBC.
  
 B) REVISE FASTENER SPACING FOR ROOF ZONE #2 (7.5").
 FASTENER SPACING NEEDS TO BE ROUNDED DOWN TO THE NEXT
 WHOLE NUMBER AS REQUIRED BY RAS 117 SEC. 10.4.5.
  
 C) ENGINEER TO CLARIFY WHY REFERENCING TWO DIFFERENT
 NOA'S. ONLY ONE WAS SUBMITTED. ALSO, SPECIFIED
 MATERIALS ARE FOR TAMKO PRODUCTS. SEE GAF NOA SUBMITTED
 AND SPECIFY CORRECT MATERIALS.
  
 D) PROVIDE 2 NEW REVISED RAS 117 CALCULATIONS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER