| 2011-10-19 09:54:49 | 7400 GEORGIA AVENUE | | | PERMIT #11100374 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ADDRESS ON PLANS (1400 GEORGIA AVENUE) DOES NOT MATCH | | | THE ADDRESS ON THE PERMIT APPLICATION. | | | | | | PER SECTION 40.2.4.1.2 (NFPA 101) A SINGLE MEANS OF | | | EGRESS FROM ANY STORY IS ONLY PERMITTED IN AN | | | UNSPRINKLERED INDUSTRIAL OCCUPANCY WHEN THE EXIT CAN BE | | | REACHED WITHIN 50 FEET OF TRAVEL; OTHERWISE, A | | | FIRE-RATED STAIR ENCLOSURE IS REQUIRED. | | | | | | GUARDS SHALL BE DESIGNED TO RESIST THE PASSAGE OF A | | | 4-INCH SPHERE UP TO A HEIGHT OF 34-INCHES. | | | | | | PROVIDE A HANDRAIL DETAIL. NOTE: HANDRAILS ARE REQUIRED | | | ON BOTH SIDES OF THE STAIR. HANDRAILS SHALL BE LOCATED | | | NOT LESS THAN 34 INCHES AND NOT MORE THAN 38 INCHES | | | ABOVE THE SURFACE OF THE TREAD, MEASURED VERTICALLY TO | | | THE TOP OF THE RAIL FROM THE LEADING EDGE OF THE TREAD. | | | HANDRAIL ENDS SHALL BE RETURNED TO THE WALL OR FLOOR OR | | | SHALL TERMINATE AT NEWEL POSTS. HANDRAIL CROSS SECTION | | | SHALL HAVE A DIAMETER OF NOT LESS THAN 1.25 INCHES AND | | | NOT MORE THAN 2 INCHES. | | | | | | PROVIDE EMERGENCY LIGHTS AND EXIT SIGNS FROM MEZZANINE. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|