Plan Review Notes
Plan Review Notes For Permit 11100374
Permit Number 11100374
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-10-19 09:54:497400 GEORGIA AVENUE
 PERMIT #11100374
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ADDRESS ON PLANS (1400 GEORGIA AVENUE) DOES NOT MATCH
 THE ADDRESS ON THE PERMIT APPLICATION.
  
 PER SECTION 40.2.4.1.2 (NFPA 101) A SINGLE MEANS OF
 EGRESS FROM ANY STORY IS ONLY PERMITTED IN AN
 UNSPRINKLERED INDUSTRIAL OCCUPANCY WHEN THE EXIT CAN BE
 REACHED WITHIN 50 FEET OF TRAVEL; OTHERWISE, A
 FIRE-RATED STAIR ENCLOSURE IS REQUIRED.
  
 GUARDS SHALL BE DESIGNED TO RESIST THE PASSAGE OF A
 4-INCH SPHERE UP TO A HEIGHT OF 34-INCHES.
  
 PROVIDE A HANDRAIL DETAIL. NOTE: HANDRAILS ARE REQUIRED
 ON BOTH SIDES OF THE STAIR. HANDRAILS SHALL BE LOCATED
 NOT LESS THAN 34 INCHES AND NOT MORE THAN 38 INCHES
 ABOVE THE SURFACE OF THE TREAD, MEASURED VERTICALLY TO
 THE TOP OF THE RAIL FROM THE LEADING EDGE OF THE TREAD.
 HANDRAIL ENDS SHALL BE RETURNED TO THE WALL OR FLOOR OR
 SHALL TERMINATE AT NEWEL POSTS. HANDRAIL CROSS SECTION
 SHALL HAVE A DIAMETER OF NOT LESS THAN 1.25 INCHES AND
 NOT MORE THAN 2 INCHES.
  
 PROVIDE EMERGENCY LIGHTS AND EXIT SIGNS FROM MEZZANINE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  