| Plan Review Notes For Permit 11100370 |
| Permit Number |
11100370 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2012-01-13 13:30:26 | BUILDING PLAN REVIEW | | | PERMIT: 11100370 | | | ADD: 215 CLEMATIS ST | | | CONT: L B DEVELOPMENT | | | TEL: (954)709-1926 | | | | | | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 01/13/2012 | | | 3RD REVIEW | | | ACTION: APPROVED | | | | | | 1) PROVISO:THE MEZZANINE AND KITCHEN BELOW MUST | | | MAINTAIN A FINISHED CEILING HEIGHT OF 7'-0" FBC-B | | | 1208.2 EXCEPTION # 3. SHEET A-3 STILL INDICATES A 6'-8" | | | DIMENSION. | | | | | | 2-4) COMPLIED. | | | | | | | | | | | | 5) BUILDING PROVISO: | | | MISSING PRODUCT APPROVALS FBC-B 1609 COMPONENTS & | | | CLADDING, RULE 9N-3. | | | 5A-B) COMPLIED. | | | 5C) EXTERIER WALK IN COOLERS &/FREEZERS | | | | | | 6-12) COMPLIED. | | | | | | 13) PROVISO: A SEPERATE PREMIT IS REQUIRED. SHEET A-3 & | | | A-4 INDICATE THE USE OF DRYWALL DROPED CEILING PANELS | | | WITH LATTICE, A NOTE ON A-3 INDICATES METHOD OF | | | ATTACHMENT, SUSPENSION BY OTHERS, THIS SYSTEM TO BE | | | REVIEWED BY THE DESIGN PROFESSIONAL, IT CAN BE | | | PERMITTED UNDER THIS PERMIT OR COME IN AS A STAND ALONE | | | PERMIT. THE DROPPED CEILING WILL NEED TO SHOW | | | COMPLIANCE WITH | | | 803.3 & 803.4.1 AND MEET THE FINISH REQUIREMENTS OF | | | TABLE 803.5. | | | | | | 14-15) COMPLIED. | | | | | | | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|