| Notes |
| Date |
Text |
| 2011-11-16 15:11:15 | PLANS DENIED | | | 1) SEPARATE PLANS AND PERMIT REQUIRED FOR HOOD AND FIRE | | | SUPPRESSION. | | | 2) REFER TO SECTION 304.10 GUARDS . IN REGARDS TO ROOF | | | PLAN PAGE M2.1 | | | 3) REFER TO SECTION 506.3.12.3 TERMINATION LOCATION. IN | | | REGARDS TO GREASE DUCT | | | ROOF PLAN PAGE M2.1 | | | 4) AIR DISTRIBUTION SCHEDULE PAGE M6.1 DOES NOT MATCH | | | THE PLANS. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|