| 2011-10-20 13:01:00 | 215 CLEMATIS STREET |
| | PERMIT #11100370 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NOTE: THIS IS A CHANGE OF OCCUPANCY FROM MERCANTILE TO |
| | ASSEMBLY. |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR TRUSS CONSTRUCTION |
| | SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO THE |
| | BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE LETTER "F" DESIGNATION |
| | PER FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE |
| | CODE 69A-60.0081. |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| | LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL |
| | CONTRAST THE BACKGROUND |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | VERIFY NO OTHER LOCKS OR LATCHES ARE INSTALLED ON THE |
| | EXISTING EXIT DOORS WITH PANIC HARDWARE. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | PROVIDE STAIR AND HANDRAIL DETAILS. |
| | |
| | INTERIOR WALL AND CEILING FINISHES SHALL MEET AT LEAST |
| | A CLASS C RATING FOR FLAME SPREAD AND SMOKE |
| | DEVELOPEMENT. |
| | |
| | SHEET A-2: INDICATE THE LOCATIONS OF WHEELCHAIR |
| | SEATING. |
| | |
| | SHEET A-2 (DOOR #2 AND #6): DURING ITS SWING, ANY DOOR |
| | IN A MEANS OF EGRESS SHALL PROJECT NOT MORE THAN |
| | 7-INCHES INTO THE REQUIRED WIDTH OF THE EGRESS PATH |
| | WHEN FULLY OPEN. |
| | |
| | SHEET A-4: HEADROOM SHALL BE NOT LESS THAN 7'-6" WITH |
| | PROJECTIONS FROM THE CEILING NOT LESS THAN 6'-8" ABOVE |
| | THE FLOOR. THE MINIMUM CEILING HEIGHT SHALL BE |
| | MAINTAINED FOR NOT LESS THAN TWO-THIRDS OF THE CEILING |
| | AREA OF ANY ROOM OR SPACE. |
| | |
| | SHEET FS-1.0: DEEP FAT FRYERS SHALL BE EQUIPPED WITH A |
| | SEPARATE HIGH-LIMIT CONTROL IN ADDITION TO THE |
| | ADJUSTABLE THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN |
| | THE FAT TEMPERATURE REACHES 475F DEGREES AT 1 INCH |
| | BELOW THE SURFACE. |
| | |
| | SHEET FS-1.0: PROVIDE AN 8? TALL STEEL BAFFLE OR |
| | PROVIDE 16? OF SPACE BETWEEN THE DEEP FAT FRYER AND |
| | SURFACE FLAMES OF THE ADJACENT EQUIPMENT. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |