| Plan Review Notes For Permit 11100290 |
| Permit Number |
11100290 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-10-26 13:17:01 | 2275 PALM BEACH LAKES BOULEVARD - SUITE "A" | | | PERMIT #11100290 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PER TABLE 6.1.14.4.1(B) OF NFPA 101 - FLORIDA EDITION, | | | THE FIRE RATED SEPARATION BETWEEN BUSINESS USE AND | | | MERCANTILE USE SHOULD BE 2-HOURS. | | | | | | VERIFY HOW DOOR LOCKS/LATCHES ON EXISTING ENTRY | | | DOORS.THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN | | | THE DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. | | | THE RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF | | | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING | | | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF | | | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE | | | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST | | | TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA | | | EDITION 2007. | | | | | | NOTE: THE PROPOSED ASSEMBLY USE IN PHASE II WILL | | | REQUIRE A FIRE ALARM SYSTEM WITH VOICE EVACUATION AND | | | AN AUTOMATIC FIRE SPRINKLER SYSTEM. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|