| 2011-10-13 10:33:15 | BUILDING PLAN REVIEW |
| | PERMIT: 11100235 |
| | ADD: 777 S FLAGLER PENTHOUSE CLUB LEVEL EAST TOWER |
| | CONT: TBD |
| | TEL: (561)856-6655 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) CONTRACTOR TO BE SIGNED ON WITH THE CORRECT |
| | LICENSURE BEFORE THE ISSUANCE OF THIS PERMIT. |
| | |
| | 2) THE PERMIT APPLICATION INDICATES INSTALL NEW |
| | RAILING? IS THIS A REPLACEMENT OF EXISTING BALCONY |
| | RAILING? NO DETAILS WERE SUBMITTED FOR HEIGHT NOR FOR |
| | ANCHORING OR |
| | COMPLIANCE WITH 1013.1 NOR 1607.7. |
| | |
| | 3) SHEET A-1.01 WIND DESIGN CRITERIA INDICATES +/- 850 |
| | F.S.P., PLANS DO NOT GIVE AN ABBREVIATION SHEET |
| | INDICATING WHAT F.S.P. STANDS FOR. ADDITIONAL |
| | INFORMATION REQUIRED. 106.1.2. |
| | |
| | 4) CONTRACTOR ONCE PICKED WILL NEED TO SUBMIT ARCH |
| | PRODUCT APPROVAL, CIRCLE THE GLAZING SYSTEM TO BE |
| | INSTALLED. COMPONENTS & CLADDING 1609. |
| | |
| | 5) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9N-3 (OLD RULE 9B-72) SHALL |
| | BE REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |