2011-11-09 15:41:311 NORTH CLEMATIS STREET - SUITE #110
 PERMIT #11100232
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT ACCURATE AS-BUILTS AND HYDRAULIC
 CALCULATIONS*****
  
 FIRE PUMP APPEARS TO BE 750 GPM AT 80 PSI, NOT 500 GPM
 AT 125 PSI AS INDICATED ON PLANS. FIELD VERIFY.
  
 PLANS SHOW ALL BRANCH LINE PIPES TO BE 1-INCH; HOWEVER
 HYDRAULIC CALCULATIONS INDICATE PIPE SIZES TO BE
 1-1/4".
  
 THE HYDRAULIC CALCULATIONS INDICATE THE CROSS MAIN SIZE
 TO BE 4"; HOWEVER, THE PLANS INDICATE THE MAIN SIZE TO
 BE 1-1/2" FOR NODES 3 TO 1 TO TOR.
  
 THE POINT TO POINT HYDRAULIC CONNECTIONS NEED TO
 CORRECTED. NODE 100 SHOULD NOT CONNECT TO NODE 103.
 NODE 1 IS NOT CONNECTED TO NODE 3.
  
 THE LOCATION OF THE NODES LABELING THE PUMP, TOP OF
 RISER AND BOTTOM OF RISER ARE NOT SHOWN IN THE ACCURATE
 LOCATION.
  
 THE EXISTING SPRINKLER DESIGN APPEARS TO BE A GRID
 SYSTEM. THE SUBMITTED PLAN SHOWS A TREE SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW