| Plan Review Notes For Permit 11100232 |
| Permit Number |
11100232 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2011-11-09 15:41:31 | 1 NORTH CLEMATIS STREET - SUITE #110 | | | PERMIT #11100232 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO - SUBMIT ACCURATE AS-BUILTS AND HYDRAULIC | | | CALCULATIONS***** | | | | | | FIRE PUMP APPEARS TO BE 750 GPM AT 80 PSI, NOT 500 GPM | | | AT 125 PSI AS INDICATED ON PLANS. FIELD VERIFY. | | | | | | PLANS SHOW ALL BRANCH LINE PIPES TO BE 1-INCH; HOWEVER | | | HYDRAULIC CALCULATIONS INDICATE PIPE SIZES TO BE | | | 1-1/4". | | | | | | THE HYDRAULIC CALCULATIONS INDICATE THE CROSS MAIN SIZE | | | TO BE 4"; HOWEVER, THE PLANS INDICATE THE MAIN SIZE TO | | | BE 1-1/2" FOR NODES 3 TO 1 TO TOR. | | | | | | THE POINT TO POINT HYDRAULIC CONNECTIONS NEED TO | | | CORRECTED. NODE 100 SHOULD NOT CONNECT TO NODE 103. | | | NODE 1 IS NOT CONNECTED TO NODE 3. | | | | | | THE LOCATION OF THE NODES LABELING THE PUMP, TOP OF | | | RISER AND BOTTOM OF RISER ARE NOT SHOWN IN THE ACCURATE | | | LOCATION. | | | | | | THE EXISTING SPRINKLER DESIGN APPEARS TO BE A GRID | | | SYSTEM. THE SUBMITTED PLAN SHOWS A TREE SYSTEM. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|