2011-11-03 14:54:271 NORTH CLEMATIS STREET - SUITE #110
 PERMIT #11100232
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL OF THE HYDRAULIC NODES ARE LABELED AS NUMBER 1.
  
 THE MIDDLE BRANCH LINE IN THE MAIN SEATING AREA IS NOT
 CONNECTED TO THE CROSS MAIN.
  
 IT APPEARS A SPRINKLER IS NEEDED IN THE DROP SOFFIT
 LOCATED NEAR THE EAST EXIT DOOR AS THE UPPER CEILING
 SPRINKLER SPRAY WOULD BE OBSTRUCTED.
  
 THE DRAWING SCALE IS INDICATED AS 3/16" = 1'-0". THE
 ACTUAL SCALE APPEARS TO BE 1/4"=1'-0".
  
 A SIX-FOOT DIAMETER FIXTURE (X3) IS SHOWN ON THE PLANS.
 ADDITIONAL SPRINKLERS MAY BE REQUIRED AROUND THE
 FIXTURE TO ACCOUNT FOR OBSTRUCTED SPRAY. PROVIDE DETAIL
 OR ADD SPRINKLERS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  