| Plan Review Notes For Permit 11100232 |
| Permit Number |
11100232 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-11-03 14:54:27 | 1 NORTH CLEMATIS STREET - SUITE #110 | | | PERMIT #11100232 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ALL OF THE HYDRAULIC NODES ARE LABELED AS NUMBER 1. | | | | | | THE MIDDLE BRANCH LINE IN THE MAIN SEATING AREA IS NOT | | | CONNECTED TO THE CROSS MAIN. | | | | | | IT APPEARS A SPRINKLER IS NEEDED IN THE DROP SOFFIT | | | LOCATED NEAR THE EAST EXIT DOOR AS THE UPPER CEILING | | | SPRINKLER SPRAY WOULD BE OBSTRUCTED. | | | | | | THE DRAWING SCALE IS INDICATED AS 3/16" = 1'-0". THE | | | ACTUAL SCALE APPEARS TO BE 1/4"=1'-0". | | | | | | A SIX-FOOT DIAMETER FIXTURE (X3) IS SHOWN ON THE PLANS. | | | ADDITIONAL SPRINKLERS MAY BE REQUIRED AROUND THE | | | FIXTURE TO ACCOUNT FOR OBSTRUCTED SPRAY. PROVIDE DETAIL | | | OR ADD SPRINKLERS. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|