| Plan Review Notes For Permit 11100221 |
| Permit Number |
11100221 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-10-18 08:45:34 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. SEE INSTALLATION SCHEDULE SUBMITTED, OPENING 1. A 3" | | | EDGE DISTANCE, 120" OPENING, WOULD HAVE A SPAN OF 123" | | | MINIMUM. THIS COMMENT APPLIES TO ALL OPENINGS. | | | | | | 2. SEE OPENING 1, "1" IS NOTED AS THE MOUNTING | | | CONNECTION TYPE. THIS IS A HEADER CONNECTION. WALL | | | MOUNT 3 (SILL) IS HIGHLIGHTED ON THE PRODUCT APPROVAL. | | | A SPAN OF 11' REQUIRES 8" ANCHOR SPACING FOR DESIGN | | | PRESSURE UP TO 40. PLEASE REVISE AND CHECK ALL | | | (ESPECIALLY OPENINGS WITH DESIGN PRESSURE GREATER THAN | | | 40). | | | | | | ANOTHER EXAMPLE, OPENING 2, WALL MOUNT 3 (HIGHLIGHTED) | | | REQUIRES 7" ANCHOR SPACING FOR DP UP TO 60, OPENING UP | | | TO 8'. | | | | | | |
|