Plan Review Notes
Plan Review Notes For Permit 11100171
Permit Number 11100171
Review Stop P
Sequence Number 1
Notes
Date Text
2011-10-28 10:48:53FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. PLANS ARE UNCLEAR AS TO THE ROOF DRAINS. IF THEY ARE
 NOT EXISTING, PLUMBING DRAWINGS WILL BE REQUIRED TO
 SHOW PIPEING FOR ROOF DRAINS.
  
 2. SEE FBC PLUMBING TABLE 1106.7 , ROOF STORM DRAIN
 CHART. SIZING APPEARS
 INCORRECT. NOTE THAT "HEAD" IN THE CHART REFERS TO
 HYDRAULIC HEAD, TO BE MEASURED 6' FROM THE SCUPPER, PER
 PLUMBING CODE COMMENTARY.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR