Plan Review Notes
Plan Review Notes For Permit 11100171
Permit Number 11100171
Review Stop B
Sequence Number 1
Notes
Date Text
2011-11-01 17:32:28****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 ***COURTESY RE-REVIEW AFTER OBTAINING MORE INFORMATION
 FROM OWNER AND ENGINEER***
  
 1. REVISE PLAN TO CLARIFY SCOPE OF WORK. SEE FBC
 EXISTING BUILDING, CLASSIFY WORK, SEE FBC101.5.
  
 2. REVISE APPLICATION TO INCLUDE STRUCTURAL WORK AND
 PLUMBING, OR HAVE PLUMBING CONTRACTOR APPLY FOR
 SEPARATE PERMIT WITH DRAINAGE CALCS (SEE FIRST COMMENT
 LIST REGARDING DRAINAGE CALCS).
  
 3. PANIC HARDWARE REQUIRED FOR ASSEMBLY OCCUPANCY, SEE
 FBC EXISTING BUILDING 302.1, 705.4.4, 705.4.4.1. A
 COMPREHENSIVE CHECKLIST CANNOT BE PROVIDED AT THIS TIME
 DUE TO INSUFFICIENT INFORMATION ON THE PLAN. THE DOOR
 PRODUCT APPROVALS DO NOT INCLUDE PANIC HARDWARE, PLEASE
 ADDRESS.
  
  
  
  
2011-10-21 16:29:09****CORRECTIONS****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE CLARIFY SCOPE OF WORK. APPLICATION STATES
 THAT THIS PERMIT IS FOR DOORS AND WINDOWS, BUT THE
 PLANS SHOW ROOF DRAINS, NEW SCUPPERS, ETC. REVISE
 PERMIT APPLICATION AND/OR PLAN TO CLEARLY SHOW SCOPE.
  
 2. SEE FBC PLUMBING TABLE 1106.7 (PER FBC 1503.4) AND
 SHEET A1, ROOF STORM DRAIN CHART. SIZING APPEARS
 INCORRECT. NOTE THAT "HEAD" IN THE CHART REFERS TO
 HYDRAULIC HEAD, TO BE MEASURED 6' FROM THE SCUPPER, PER
 PLUMBING CODE COMMENTARY.
  
 3. OUR RECORDS SHOW THAT THIS ROOF HAS OBTAINED A
 CERTIFICATE OF COMPLETION FOR A REROOF WITH PROVISO
 THAT SCUPPERS AND ROOF DRAINS TO BE ON SEPARATE PERMIT,
 BUT ENGINEER OF RECORD STATED THAT THE ROOF WAS
 PATCHED. PLEASE ADDRESS ROOF DRAINAGE AND CONFIRM THAT
 THE ROOF CURRENTLY HAS POSITIVE DRAINAGE.
  
 4. APPLICATION STATES THAT FOUR 52" COLUMNS ARE TO BE
 INSTALLED, NOTHING WHICH FITS THIS DESCRIPTION IS ON
 THE PLAN.
  
 5. MORE INFORMATION REGARDING THE PROPOSED OCCUPANCY
 AND OCCPUANT LOAD IN ORDER TO DETERMINE WHETHER OR NOT
 PANIC DEVICES ARE REQUIRED ON THE DOORS. EITHER PROVIDE
 A LIFE SAFETY PLAN OR, ALTERNATIVELY, INCLUDE PANIC
 DEVICES ON THE DOOR SCHEDULE AND PRODUCT APPROVALS
 WHICH INCLUDE PANIC DEVICES.
  
  