| 2011-10-19 15:28:50 | 11100165 | | | 2416 MEDINA WAY | | | INTERIOR RESIDENTIAL RENOVATION | | | | | | VERIFY THE EXISTING LIVING ROOM BEING RENOVATED HAS | | | RECEPTACLES PROPERLY SPACED. NEC 210.52 | | | VERIFY OR PROVIDE SMOKE DETECTORS AND CARBON MONOXIDE | | | DETECTORS AS REQUIRED FOR ADDITIONS AND RENOVATIONS. | | | FBC R 313.2.1, R313.4 | | | VERIFY THAT COUNTER TOP RECEPTACLES ARE GFCI PROTECTED | | | AND DISTRIBUTED APPROPRIATELY. NEC 210.8, 210.52 | | | VERIFY OR PROVIDE A GFCI PROTECTED RECEPTACLE ON THE | | | NEW TERRACE. NEC 210.8 | | | PROVIDE SPECIFICATIONS ON THE TERRACE CEILING FANS | | | INDICATING THE EQUIPMENT IS SUITABLE FOR USE IN A DAMP | | | LOCATION. NEC 110.11 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|