| Plan Review Notes For Permit 11100150 |
| Permit Number |
11100150 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-11-07 16:15:08 | AN ELECTRIC PLAN WITH A LAYOUT, SERVICE RISER, PANEL | | | SCHEDULE AND LOAD CALCULATION SHOWING THE EXISTING | | | ELECTRICAL SYSTEM AS MEETING THE REQUIREMENTS OF THE | | | 2008 NATIONAL ELECTRICAL CODE IS REQUIRED. NEC 215.5 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|