Plan Review Notes
Plan Review Notes For Permit 11100139
Permit Number 11100139
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-10-13 15:39:231691 FORUM PLACE - SUITE "B"
 PERMIT #11100139
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND/OR FIRE
 ALARM SYSTEM.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  