| Plan Review Notes For Permit 11100120 |
| Permit Number |
11100120 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-10-06 10:48:30 | REPAIRS AS REQUIRED FROM RED TAG: | | | 1) REPAIR WIRES TO PANEL, TO SMALL, WAS SPLICED WITH | | | #6, NEEDS TO BE SPLICED WITH #4 | | | 2) ADD SMOKE DETECTORS | | | 3) 4 WIRES TO RANGE, REPLACE 8/2 TO 8/3 WITH FOUR | | | PROUNG OUTLET | | | 4) WIRES TO WATER HEATER ARE TO SMALL FOR ELEMENT: | | | CONTRACTOR INDICATES THAT PLUMBING CONTRACTOR WILL COME | | | IN TO CHANGE THE ELEMENTS TO THE CORRCT SIZE FOR | | | EXISTING WIRING AS STATED ON PLANS. |
|