2011-10-12 14:56:56FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET 2 NEW ADDED DOUBLE SINK IS SHOWN CONNECTED TO
 THE RESTROOM WET VENT SYSTEM.
 909.1 HORIZONTAL WET VENT PERMITTED.
 ....ANY ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM
 OF THE HORIZONTAL WET VENT.
  
 2. SHEET 1THE RECONFIGURED RESTROOM WITH A WIDTH OF
 4'-0" WOULD NOT COMPLY WITH 405.3.1. MINIMUM WIDTH
 WOULD BE 5'-0".
 405.3.1 WATER CLOSETS, URINALS, LAVATORIES AND BIDETS.
 A WATER CLOSET, URINAL, LAVATORY OR BIDET SHALL NOT BE
 SET CLOSER THAN 15 INCHES (381 MM) FROM ITS CENTER TO
 ANY SIDE WALL, PARTITION, VANITY OR OTHER OBSTRUCTION,
 OR CLOSER THAN 30 INCHES (762 MM) CENTER-TO-CENTER
 BETWEEN ADJACENT FIXTURES. THERE SHALL BE AT LEAST A
 21-INCH (533 MM) CLEARANCE IN FRONT OF THE WATER
 CLOSET, URINAL, LAVATORY OR BIDET TO ANY WALL, FIXTURE
 OR DOOR. WATER CLOSET COMPARTMENTS SHALL NOT BE LESS
 THAN 30 INCHES (762 MM) WIDE AND 60 INCHES (1524 MM)
 DEEP (SEE FIGURE 405.3.1).
  