| Plan Review Notes For Permit 11100119 |
| Permit Number |
11100119 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-10-12 14:56:56 | FBC 2007 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. SHEET 2 NEW ADDED DOUBLE SINK IS SHOWN CONNECTED TO | | | THE RESTROOM WET VENT SYSTEM. | | | 909.1 HORIZONTAL WET VENT PERMITTED. | | | ....ANY ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM | | | OF THE HORIZONTAL WET VENT. | | | | | | 2. SHEET 1THE RECONFIGURED RESTROOM WITH A WIDTH OF | | | 4'-0" WOULD NOT COMPLY WITH 405.3.1. MINIMUM WIDTH | | | WOULD BE 5'-0". | | | 405.3.1 WATER CLOSETS, URINALS, LAVATORIES AND BIDETS. | | | A WATER CLOSET, URINAL, LAVATORY OR BIDET SHALL NOT BE | | | SET CLOSER THAN 15 INCHES (381 MM) FROM ITS CENTER TO | | | ANY SIDE WALL, PARTITION, VANITY OR OTHER OBSTRUCTION, | | | OR CLOSER THAN 30 INCHES (762 MM) CENTER-TO-CENTER | | | BETWEEN ADJACENT FIXTURES. THERE SHALL BE AT LEAST A | | | 21-INCH (533 MM) CLEARANCE IN FRONT OF THE WATER | | | CLOSET, URINAL, LAVATORY OR BIDET TO ANY WALL, FIXTURE | | | OR DOOR. WATER CLOSET COMPARTMENTS SHALL NOT BE LESS | | | THAN 30 INCHES (762 MM) WIDE AND 60 INCHES (1524 MM) | | | DEEP (SEE FIGURE 405.3.1). | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|