2011-10-24 10:32:03REVISION BUILDING REVIEW CHECKLIST
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- NEW ROOF REQUIRES ATTIC ACCESS IN PORCH AREA AND IN
 NEW ADDITION. PROVIDE FLOOR PLAN SHOWING SIZE AND
 LOCATION OF ATTIC ACCESS AS REQUIRED BY SEC. R807.
  
 2- ENGINEER TO SPECIFY ALL ROOF LOADS INCLUDING THE
 ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5 AND SEC.
 R301.2.1.4.3.
  
 3- OWES $302.03 FOR REVISION FEES.
  
  
 4- THE FOLLOWING ITEMS REQUESTED ON PROVISO WERE NOT
 ADDRESSED:
  
 A) SHEET 1 OF 6:
 (1) REVISE DOORS AND WINDOWS DESIGN PRESSURES TO MATCH
 EXPOSURE "C".
  
 (2) UPDATE GENERAL NOTES #7 AND #12: SEE THE 2007
 FLORIDA RESIDENTIAL CODE FOR CORRECT CODE SECTION.
  
 (3) UPDATE WIND INFORMATION: REVISE ALL NOTES CITING
 CORRECT TABLES AND SECTION OF THE 2007 FLORIDA
 RESIDENTIAL CODE. ALSO. REFER TO 2007 FLORIDA
 RESIDENTIAL CODE NOT 2004.
  
 B) SPECIFY SIZE OF EGRESS WINDOW ON EXISTING BEDROOM TO
 VERIFY COMPLIANCE WITH SEC. R310.
  
 C) SHEET 4 OF 6: REVISE THE FLORIDA PRODUCT APPROVAL
 NUMBERS SHOWN ON THE STRAPPING SCHEDULE. VISIT FLORIDA
 PRODUCT APPROVAL WEB PAGE AND PROVIDE CORRECT NUMBERS.
  
 D) SPECIFY ATTIC VENTILATION AS REQUIRED BY SEC. R806.
 SPECIFY SIZE OF VENTS.
  
 E) PROVIDE SURVEY WITH SURVEYOR'S ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 472 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER