| 2011-10-17 10:53:42 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. AS THIS IS A COMMERCIAL BUILDING, PROVIDE MORE |
| | INFORMATION REGARDING THE FLOOR PLAN AND EXITING. NOTE |
| | THAT THERE IS NO PROVISION FOR BLOCKING REQUIRED EXITS |
| | (COMMERCIAL) WITH HURRICANE PROTECTION, SEE FBC |
| | 1003.6,: |
| | |
| | MEANS OF EGRESS CONTINUITY. THE PATH OF EGRESS TRAVEL |
| | ALONG A MEANS OF EGRESS SHALL NOT BE INTERRUPTED BY ANY |
| | BUILDING ELEMENT OTHER THAN A MEANS OF EGRESS COMPONENT |
| | AS SPECIFIED IN THIS CHAPTER. OBSTRUCTIONS SHALL NOT BE |
| | PLACED IN THE REQUIRED WIDTH OF A MEANS OF EGRESS |
| | EXCEPT PROJECTIONS PERMITTED BY THIS CHAPTER. |
| | |
| | SEE ALSO 1008.1.3.5 SECURITY GRILLS. IN GROUPS B, F, M, |
| | R AND S, HORIZONTAL SLIDING OR VERTICAL SECURITY |
| | GRILLES ARE PERMITTED AT THE MAIN EXIT AND SHALL BE |
| | OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR |
| | SPECIAL KNOWLEDGE OR EFFORT DURING PERIODS THAT THE |
| | SPACE IS OCCUPIED. THE GRILLES SHALL REMAIN SECURED IN |
| | THE FULL-OPEN POSITION DURING THE PERIOD OF OCCUPANCY |
| | BY THE GENERAL PUBLIC. WHERE TWO OR MORE MEANS OF |
| | EGRESS ARE REQUIRED, NOT MORE THAN ONE-HALF OF THE |
| | EXITS OR EXIT ACCESS DOORWAYS SHALL BE EQUIPPED WITH |
| | HORIZONTAL SLIDING OR VERTICAL SECURITY GRILLES. |
| | |
| | PROVIDE MORE INFORMATION SUCH AS TRAVEL DISTANCE, |
| | OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, FLOOR PLAN |
| | SHOWING ALTERNATE EXITS, ETC. |
| | |
| | |