| Plan Review Notes For Permit 11100025 |
| Permit Number |
11100025 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-10-05 13:39:51 | 410 EVERNIA STREET - SUITE #108 | | | PERMIT #11100025 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE HYDRAULIC CALCULATIONS TO VERIFY THE EXISTING | | | PIPE SIZES ARE SUFFICIENT FOR THE NEW LARGER K-FACTOR | | | COMMERCIAL STYLE SPRINKLERS. | | | | | | THE COLUMN NEAR THE FIRST FLOOR BATHROOM OBSTRUCTS THE | | | SPRAY OF THE EXTENDED COVERAGE SIDEWALL SPRINKLER. | | | | | | SPRINKLER PROTECTION IS REQUIRED IN ALL THREE CLOSET | | | SPACES ON THE MEZZANINE LEVEL. | | | | | | BOTH FLOOR PLANS ON THE DRAWING ARE INDICATED AS BEING | | | THE MEZZANINE LEVEL. | | | | | | INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE FOR THIS | | | FLOOR TO BE UTILIZED FOR THE 2-HOUR PRESSURE TEST. | | | | | | FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND | | | END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE | | | PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE | | | LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE | | | THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING | | | UPWARD MOVEMENT. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|