Plan Review Notes
Plan Review Notes For Permit 11100001
Permit Number 11100001
Review Stop E
Sequence Number 1
Notes
Date Text
2011-10-04 09:17:212007 FBC W/2009 REVISIONS
 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) THE LOAD CALCULATIONS FOR ARE NOT IN COMPLIANCE WITH
 NEC 220. THE LOAD CALCULATIONS SPECIFY A 40 AMP SUB
 PANEL "B", WHICH IS TOO SMALL FOR THE LOAD OF THE
 DETACHED STORAGE ROOM. SEE NEC 220.83 (A)
  
 2) THE RISER DIAGRAM SHOWS SUB-PANEL "B" AS 25 AMPS.
 COORDINATE THE RISER DIAGRAM WITH THE CORRECTED
 CALCULATED LOADS.
  
 3) SHOW THE BREAKER THAT FEEDS SUB-PANEL "B" IN THE
 SCHEDULE FOR MAIN PANEL "A".
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]