| 2011-10-04 09:17:21 | 2007 FBC W/2009 REVISIONS | | | 2008 NEC | | | | | | DENIED BY ELECTRIC | | | | | | 1) THE LOAD CALCULATIONS FOR ARE NOT IN COMPLIANCE WITH | | | NEC 220. THE LOAD CALCULATIONS SPECIFY A 40 AMP SUB | | | PANEL "B", WHICH IS TOO SMALL FOR THE LOAD OF THE | | | DETACHED STORAGE ROOM. SEE NEC 220.83 (A) | | | | | | 2) THE RISER DIAGRAM SHOWS SUB-PANEL "B" AS 25 AMPS. | | | COORDINATE THE RISER DIAGRAM WITH THE CORRECTED | | | CALCULATED LOADS. | | | | | | 3) SHOW THE BREAKER THAT FEEDS SUB-PANEL "B" IN THE | | | SCHEDULE FOR MAIN PANEL "A". | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|