Notes
Date Text
2011-10-12 16:01:10THE DESIGN PRESSURES FOR THE PGT 770 DOES NOT MEET THE
 ENGINEERS DESIGN PRESSURES FOR THE BUILDING.
  
 ALSO THE ENGINEERS CALCULATIONS REFERENCE EXPOSURE 'B',
 I BELIEVE THE BUILDING FALLS IN CATEGORY 'C' THEREFORE
 REQUIRING AN ADDITIONAL MULTIPLIER, SEE TABLE 1609.6
 (2) 2007 FBC.
  
  
  
  
 LUIS MARTINEZ
 561-805-6710