| 2011-12-20 15:53:14 | ****CORRECTIONS**** |
| | 11090826 |
| | |
| | COMMENTS FROM PREVIOUS LIST: |
| | |
| | 1. SEPARATE PERMITS AND REVIEWS REQUIRED FOR |
| | REFRIGERATION EQUIPMENT, HOOD, AND FUEL. FDEP APPROVAL |
| | REQUIRED PRIOR TO SUBMITTAL FOR FUEL PERMIT. |
| | |
| | ADVISORY ONLY. |
| | |
| | 2. OUTSIDE AIR DUCT REQUIRES A DAMPER, FBC |
| | 13.409.AB.3.3. |
| | |
| | 2ND REVIEW, MOTORIZED DAMPERS REQUIRED. |
| | |
| | 3RD REVIEW, M2, PLAN SHOWS GRAVITY DAMPERS FOR OUTSIDE |
| | AIR, NOTE 14. SHEET M2 SHOWS 1000 CFM OUTSIDE AIR. |
| | PLEASE SEE: |
| | |
| | 13-409.AB.3.3 SHUTOFF DAMPER CONTROLS. BOTH OUTDOOR AIR |
| | SUPPLY AND EXHAUST SYSTEMS SHALL BE EQUIPPED WITH |
| | MOTORIZED DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE |
| | SYSTEMS OR SPACES SERVED ARE NOT IN USE. VENTILATION |
| | OUTSIDE AIR DAMPERS SHALL BE CAPABLE OF AUTOMATICALLY |
| | SHUTTING OFF DURING PREOCCUPANCY BUILDING WARMUP, |
| | COOLDOWN, AND SETBACK, EXCEPT WHEN VENTILATION REDUCES |
| | ENERGY COSTS (E.G., NIGHT PURGE) OR WHEN VENTILATION |
| | MUST BE SUPPLIED TO MEET CODE REQUIREMENTS. |
| | |
| | EXCEPTIONS: |
| | |
| | 1. GRAVITY (NONMOTORIZED) DAMPERS ARE ACCEPTABLE IN |
| | BUILDING EXHAUST AIR SYSTEMS. |
| | |
| | 2. GRAVITY (NONMOTORIZED) DAMPERS ARE ACCEPTABLE IN |
| | SYSTEMS WITH A DESIGN OUTSIDE AIR INTAKE OR EXHAUST |
| | CAPACITY OF 300 CFM (.14 M3/S) OR LESS. |
| | |
| | 3. OK. |
| | |
| | 4. PROVIDE A DETAIL FOR THE CURB, FBC 1609. |
| | |
| | 2ND & 3RD REVIEW, CURB DETAIL DOES NOT INCLUDE ANY |
| | FASTENING INFORMATION. SHOW HOW THE CURB WILL RESIST |
| | WIND LOADS. |
| | |
| | 5. AN ELECTRIC ROOM WITH A 1 HOUR FIRE RATED WALL HAS |
| | BEEN ADDED ON A SHEETS BUT NOT SHOWN ON M SHEETS. |
| | PLEASE SHOW FIRE RATED WALL ON M SHEETS AND FIRE |
| | DAMPERS FBC MECHANICAL TABLE 607.3.1. FLEXIBLE DUCT AND |
| | AIR CONNECTORS SHALL NOT PASS THROUGH ANY FIRE |
| | RESISTANCE RATED ASSEMBLY. |
| | |
| | HAROLD MOSER, CHIEF MECHANICAL INSPECTOR |
| | 561-805-6732 |
| | |