Plan Review Notes
Plan Review Notes For Permit 11090826
Permit Number 11090826
Review Stop M
Sequence Number 3
Notes
Date Text
2011-12-20 15:53:14****CORRECTIONS****
 11090826
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. SEPARATE PERMITS AND REVIEWS REQUIRED FOR
 REFRIGERATION EQUIPMENT, HOOD, AND FUEL. FDEP APPROVAL
 REQUIRED PRIOR TO SUBMITTAL FOR FUEL PERMIT.
  
 ADVISORY ONLY.
  
 2. OUTSIDE AIR DUCT REQUIRES A DAMPER, FBC
 13.409.AB.3.3.
  
 2ND REVIEW, MOTORIZED DAMPERS REQUIRED.
  
 3RD REVIEW, M2, PLAN SHOWS GRAVITY DAMPERS FOR OUTSIDE
 AIR, NOTE 14. SHEET M2 SHOWS 1000 CFM OUTSIDE AIR.
 PLEASE SEE:
  
 13-409.AB.3.3 SHUTOFF DAMPER CONTROLS. BOTH OUTDOOR AIR
 SUPPLY AND EXHAUST SYSTEMS SHALL BE EQUIPPED WITH
 MOTORIZED DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE
 SYSTEMS OR SPACES SERVED ARE NOT IN USE. VENTILATION
 OUTSIDE AIR DAMPERS SHALL BE CAPABLE OF AUTOMATICALLY
 SHUTTING OFF DURING PREOCCUPANCY BUILDING WARMUP,
 COOLDOWN, AND SETBACK, EXCEPT WHEN VENTILATION REDUCES
 ENERGY COSTS (E.G., NIGHT PURGE) OR WHEN VENTILATION
 MUST BE SUPPLIED TO MEET CODE REQUIREMENTS.
  
 EXCEPTIONS:
  
 1. GRAVITY (NONMOTORIZED) DAMPERS ARE ACCEPTABLE IN
 BUILDING EXHAUST AIR SYSTEMS.
  
 2. GRAVITY (NONMOTORIZED) DAMPERS ARE ACCEPTABLE IN
 SYSTEMS WITH A DESIGN OUTSIDE AIR INTAKE OR EXHAUST
 CAPACITY OF 300 CFM (.14 M3/S) OR LESS.
  
 3. OK.
  
 4. PROVIDE A DETAIL FOR THE CURB, FBC 1609.
  
 2ND & 3RD REVIEW, CURB DETAIL DOES NOT INCLUDE ANY
 FASTENING INFORMATION. SHOW HOW THE CURB WILL RESIST
 WIND LOADS.
  
 5. AN ELECTRIC ROOM WITH A 1 HOUR FIRE RATED WALL HAS
 BEEN ADDED ON A SHEETS BUT NOT SHOWN ON M SHEETS.
 PLEASE SHOW FIRE RATED WALL ON M SHEETS AND FIRE
 DAMPERS FBC MECHANICAL TABLE 607.3.1. FLEXIBLE DUCT AND
 AIR CONNECTORS SHALL NOT PASS THROUGH ANY FIRE
 RESISTANCE RATED ASSEMBLY.
  
 HAROLD MOSER, CHIEF MECHANICAL INSPECTOR