Plan Review Notes
Plan Review Notes For Permit 11090826
Permit Number 11090826
Review Stop E
Sequence Number 3
Notes
Date Text
2011-12-14 18:10:1511090826
 1270 PALM BEACH LAKES BLVD.
 NEW GASOLINE/ CONVENIENCE STORE
  
 THE FOLLOWING ITEMS HAVE NOT BEEN ADDRESSED FROM
 PREVIOUS ELECTRIC REVIEWS. PLEASE CALL ME TO DISCUSS
 FURTHER SO WE CAN EXPEDIATE THE REMAINING ITEMS.
  
 SPECIFY ON THE PLANS HOW THE INTERIOR LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. AUTOMATIC
 LIGHTING CONTROL FBC 13-415.ABC.1.1; AUTOMATIC SPACE
 CONTROL FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS
 13-412.ABC.1.3
  
 VERIFY THE SERVICE EQUIPMENT IS CAPABLE TO INTERRUPT
 THE AVAILABLE FAULT CURRENT. FPL, THE LOCAL ELECTRIC
 UTILITY, CAN PROVIDE THE AVAILABLE FAULT CURRENT AT
 THEIR POINT OF SERVICE. THE NEW SERVICE DISCONNECTS AND
 PANEL BOARDS MUST HAVE THE CAPABILITY TO INTERRRUPT THE
 AVAILABLE FAULT CURRENT. NEC 110.9
  
 THANK YOU
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718