| Plan Review Notes For Permit 11090826 |
| Permit Number |
11090826 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2011-12-14 18:10:15 | 11090826 | | | 1270 PALM BEACH LAKES BLVD. | | | NEW GASOLINE/ CONVENIENCE STORE | | | | | | THE FOLLOWING ITEMS HAVE NOT BEEN ADDRESSED FROM | | | PREVIOUS ELECTRIC REVIEWS. PLEASE CALL ME TO DISCUSS | | | FURTHER SO WE CAN EXPEDIATE THE REMAINING ITEMS. | | | | | | SPECIFY ON THE PLANS HOW THE INTERIOR LIGHTING WILL BE | | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES | | | AS REQUIRED BY THE FLORIDA BUILDING CODE. AUTOMATIC | | | LIGHTING CONTROL FBC 13-415.ABC.1.1; AUTOMATIC SPACE | | | CONTROL FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS | | | 13-412.ABC.1.3 | | | | | | VERIFY THE SERVICE EQUIPMENT IS CAPABLE TO INTERRUPT | | | THE AVAILABLE FAULT CURRENT. FPL, THE LOCAL ELECTRIC | | | UTILITY, CAN PROVIDE THE AVAILABLE FAULT CURRENT AT | | | THEIR POINT OF SERVICE. THE NEW SERVICE DISCONNECTS AND | | | PANEL BOARDS MUST HAVE THE CAPABILITY TO INTERRRUPT THE | | | AVAILABLE FAULT CURRENT. NEC 110.9 | | | | | | THANK YOU | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 |
|