| Date |
Text |
| 2011-12-20 14:52:57 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. OK. |
| | |
| | 2. WALL ORIENTATION AND FIRE RATING HAS BEEN CORRECTED, |
| | BUT NO INFORMATION PROVIDED REGARDING CUPOLA FIRE |
| | RESISTANCE, SEE FBC 704.11 AND EXCEPTIONS. |
| | |
| | COMPLIANCE WITH FBC TABLE 704.8 NOT CLEAR. IT IS NOT |
| | CLEAR WHAT PORTION OF THE ANGLED WALL IS LESS THAN 20? |
| | FROM THE PROPERTY LINE. PLEASE SHOW THE 20? LINE |
| | THROUGH THE EAST ELEVATION AND PROVIDE CALCULATION, 25 |
| | PERCENT MAXIMUM OPENINGS PERMITTED FOR TYPE VA. |
| | |
| | 3. OK |
| | |
| | 4. ORIENTATION OF STRUCTURE IS NOT CLEAR, SEE OTHER |
| | COMMENTS, BUT IT APPEARS THAT THE ONLY EXIT IS COVERED |
| | BY THE SAME STRUCTURE AS THE PROPOSED FUEL CANOPY. IS |
| | THIS CORRECT AND DESIGNER'S INTENT? |
| | |
| | 3RD REVIEW, NO RESPONSE LETTER PROVIDED. THE SECOND |
| | DOOR SHOWN IS NOT AN EXIT AS IT GOES THROUGH A KITCHEN. |
| | |
| | 5. OK. |
| | |
| | 6. A LIFE SAFETY PLAN WAS REQUESTED IN FIRST REVIEW, |
| | BUT NOT PROVIDED. HOWEVER, PLAN WAS REVISED TO INCLUDE |
| | BREAKDOWN BY AREA AND OCCUPANT LOAD. AS THE OCCUPANT |
| | LOAD EXCEEDS 49, TWO EXITS REQUIRED FBC TABLE 1015.1. |
| | |
| | 3RD REVIEW, LIFE SAFETY PLAN PROVIDED, BUT SHOWS THE |
| | SECOND EXIT IN THE KITCHEN. SEE FBC 1014.2(2), THIS IS |
| | PROHIBITED. |
| | |
| | **COURTESY REVIEW** REVISED OCCUPANT LOAD SENT VIA |
| | EMAIL ON 12/15 SHOWS 1339 SF WITH AN OCCUPANT LOAD OF |
| | 45. IF THE BUILDING IS 2505 SF (FROM SHEET A-1C AND |
| | OTHER SHEETS) AND THE COOLER IS 335 SF, THAT LEAVES |
| | 2170 SF OF OCCUPIED SPACE. PLEASE INCLUDE OCCUPANTS FOR |
| | THE ADDITIONAL 831 SF WHICH APPEARS TO BE MISSING FROM |
| | THE CALCULATION. |
| | |
| | 7. SEE ITEM 6. |
| | |
| | 8. OK. |
| | |
| | 9. OK. |
| | |
| | 10. PROVIDE PRODUCT APPROVALS FOR ALL COMPONENTS AND |
| | CLADDING, FBC1609 (DOORS, STOREFRONT, DRIVE THROUGH |
| | WINDOW, BULLET PROOF/IMPACT WINDOWS, ROOF, ROOF STANDS, |
| | ETC.). |
| | |
| | 3RD REVIEW, SOME BUT NOT ALL PRODUCT APPROVALS WERE |
| | SUBMITTED. PLEASE NOTE THAT ANY PRODUCT APPROVALS WHICH |
| | HAVE NOT BEEN SUBMITTED PRIOR TO ISSUANCE WILL BE |
| | REQUIRED TO BE SUBMITTED AS A REVISION. |
| | |
| | 11. PROVIDE DETAILS FOR THE FIRE RATED WALLS AND OTHER |
| | ELEMENTS REQUIRED FOR BUILDING TYPE VA, FBC 703. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. |
| | |
| | 3RD REVIEW, NOT ADDRESSED. AN INTERIOR FIRE RATED |
| | PARTITION WALL IS INCLUDED. I WAS UNABLE TO LOCATE THE |
| | FIRE RATING DETAILS FOR STRUCTURAL ELEMENTS. NOTE THAT |
| | THE FUEL CANOPY IS A PART OF THE BUILDING AND REQUIRES |
| | THE SAME FIRE RATING. |
| | |
| | IT IS NOT CLEAR WHY THIS BUILDING IS TYPE VA. IF YOU |
| | NEED ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME TO |
| | DISCUSS OPTIONS. |
| | |
| | 12. IMPACT FEE ASSESSMENT REQUIRED, PLEASE CONTACT PALM |
| | BEACH COUNTY, 561 233 5025. |
| | |
| | 3RD REVIEW, COULD NOT LOCATE IMPACT FEE STAMP (LOOKED |
| | IN BOTH SETS OF NEW PLANS) OR THE RECEIPT. PLEASE |
| | PROVIDE. |
| | |
| | 13. PROVIDE A SOILS INVESTIGATION REPORT, FBC 1802.4. |
| | |
| | 2ND & 3RD REVIEWS, NOT ADDRESSED. |
| | |
| | 14. SEE FBC 11-4.7, CURB RAMP REQUIRED WHERE ACCESSIBLE |
| | ROUTE CROSSES A CURB. |
| | |
| | 3RD REVIEW, NOT ADDRESSED. |
| | |
| | 15. (NEW COMMENT ON NEW DOCUMENTS) DELEGATED |
| | ENGINEERING TO BE REVIEWED BY ENGINEER OF RECORD, |
| | FAC61G. |
| | |
| | 16. (NEW COMMENT ON NEW DETAIL) S1 SHOWS A HAND DRAWN |
| | ATM MACHINE BETWEEN THE BATHROOM AND THE WATER |
| | FOUNTAIN. SEE FBC 11 FIGURE 27 AND FIGURE 25 FOR CLEAR |
| | FLOOR SPACE AND MANEUVERING CLEARANCE REQUIREMENTS. |
| | ELECTRICAL SHEETS STILL SHOW ATM IN OLD LOCATION. |
| | |
| | ***WHEN RESUBMITTING, PLEASE INCLUDE A WRITTEN RESPONSE |
| | LETTER.*** |
| | |
| | |