2011-12-08 10:39:01****CORRECTIONS****
 11090826
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. SEPARATE PERMITS AND REVIEWS REQUIRED FOR
 REFRIGERATION EQUIPMENT, HOOD, AND FUEL. FDEP APPROVAL
 REQUIRED PRIOR TO SUBMITTAL FOR FUEL PERMIT.
  
 ADVISORY ONLY.
  
 2. OUTSIDE AIR DUCT REQUIRES A DAMPER, FBC
 13.409.AB.3.3.
  
 2ND REVIEW, MOTORIZED DAMPERS REQUIRED.
  
 3. SHOW CONDENSATE DISCHARGE, FBC MECHANICAL 307.2.1.
  
 2ND REVIEW, CONDENSATE CANNOT DISCHARGE INTO SANITARY,
 CITY OF WEST PALM BEACH MUNICIPAL CODE 90-125.
  
 4. PROVIDE A DETAIL FOR THE CURB, FBC 1609.
  
 2ND REVIEW, CURB DETAIL DOES NOT INCLUDE ANY FASTENING
 INFORMATION. SHOW HOW THE CURB WILL RESIST WIND LOADS.
  
 HAROLD MOSER, CHIEF MECHANICAL INSPECTOR