| Plan Review Notes For Permit 11090826 |
| Permit Number |
11090826 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-12-08 10:39:01 | ****CORRECTIONS**** | | | 11090826 | | | | | | COMMENTS FROM PREVIOUS LIST: | | | | | | 1. SEPARATE PERMITS AND REVIEWS REQUIRED FOR | | | REFRIGERATION EQUIPMENT, HOOD, AND FUEL. FDEP APPROVAL | | | REQUIRED PRIOR TO SUBMITTAL FOR FUEL PERMIT. | | | | | | ADVISORY ONLY. | | | | | | 2. OUTSIDE AIR DUCT REQUIRES A DAMPER, FBC | | | 13.409.AB.3.3. | | | | | | 2ND REVIEW, MOTORIZED DAMPERS REQUIRED. | | | | | | 3. SHOW CONDENSATE DISCHARGE, FBC MECHANICAL 307.2.1. | | | | | | 2ND REVIEW, CONDENSATE CANNOT DISCHARGE INTO SANITARY, | | | CITY OF WEST PALM BEACH MUNICIPAL CODE 90-125. | | | | | | 4. PROVIDE A DETAIL FOR THE CURB, FBC 1609. | | | | | | 2ND REVIEW, CURB DETAIL DOES NOT INCLUDE ANY FASTENING | | | INFORMATION. SHOW HOW THE CURB WILL RESIST WIND LOADS. | | | | | | HAROLD MOSER, CHIEF MECHANICAL INSPECTOR | | | 561-805-6732 | | | | | | |
|