2011-11-15 11:01:151270 PALM BEACH LAKES BOULEVARD
 PERMIT #11090826
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 WORKING AND TESTED WET FIRE HYDRANT REQUIRED PRIOR TO
 CONSTRUCTION.
  
 COMMERCIAL COOKING EQUIPMENT AND EXHAUST HOOD REQUIRED
 TO BE PROTECTED BY A UL 300 LISTED SUPPRESSION SYSTEM.
 SEPARATE PLANS AND PERMITS NEEDED FOR HOOD AND
 SUPPRESSION SYSTEM.
  
 PROVIDE AN 8" TALL STEEL BAFFLE OR PROVIDE 16" OF SPACE
 BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE
 ADJACENT EQUIPMENT.
  
 SHEET LS-1: THE FIRE HYDRANT SHALL BE PROVIDED WITH
 CLEARANCES OF THE 7'-6" TO THE SIDES/FRONT AND 4'-0" TO
 THE REAR. THE LANDSCAPE PLAN APPEARS TO HAVE A FLORIDA
 ROYAL PALM IN FIRE HYDRANT CLEARANCE AREA.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW