| Plan Review Notes For Permit 11090826 |
| Permit Number |
11090826 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-11-15 11:38:14 | ELECTRIC PLAN REVIEW COMMENTS FROM PREVIOUS REVIEW OF | | | 10/3/11 AS NOTED BELOW WERE NOT ADDRESSED WITHIN THE | | | RESUBMITTAL. | | | | | | | | | 11090826 | | | 1270 PALM BEACH LAKES BLVD. | | | NEW GASOLINE/ CONVENIENCE STORE | | | | | | SPECIFY ON THE PLANS HOW THE INTERIOR AND EXTERIOR | | | LIGHTING WILL BE CONTROLLED USING MOTION SENSORS OR | | | SIMILAR TECHNIQUES AS REQUIRED BY THE FLORIDA BUILDING | | | CODE. AUTOMATIC LIGHTING CONTROL FBC 13-415.ABC.1.1; | | | AUTOMATIC SPACE CONTROL FBC 13-415 ABC.1.2; ADDITIONAL | | | CONTROLS 13-412.ABC.1.3 | | | VERIFY THE SERVICE EQUIPMENT IS CAPABLE TO INTERRUPT | | | THE AVAILABLE FAULT CURRENT. FPL, THE LOCAL ELECTRIC | | | UTILITY, CAN PROVIDE THE AVAILABLE FAULT CURRENT AT | | | THEIR POINT OF SERVICE. NEC 110.9 | | | PROVIDE A DEDICATED SPACE FOR THE SERVICE PANEL BOARDS. | | | NEC 110. 26 (F) | | | PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE | | | GROUND. NEC 250.94 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | |
|