2011-11-15 11:38:14ELECTRIC PLAN REVIEW COMMENTS FROM PREVIOUS REVIEW OF
 10/3/11 AS NOTED BELOW WERE NOT ADDRESSED WITHIN THE
 RESUBMITTAL.
  
  
 11090826
 1270 PALM BEACH LAKES BLVD.
 NEW GASOLINE/ CONVENIENCE STORE
  
 SPECIFY ON THE PLANS HOW THE INTERIOR AND EXTERIOR
 LIGHTING WILL BE CONTROLLED USING MOTION SENSORS OR
 SIMILAR TECHNIQUES AS REQUIRED BY THE FLORIDA BUILDING
 CODE. AUTOMATIC LIGHTING CONTROL FBC 13-415.ABC.1.1;
 AUTOMATIC SPACE CONTROL FBC 13-415 ABC.1.2; ADDITIONAL
 CONTROLS 13-412.ABC.1.3
 VERIFY THE SERVICE EQUIPMENT IS CAPABLE TO INTERRUPT
 THE AVAILABLE FAULT CURRENT. FPL, THE LOCAL ELECTRIC
 UTILITY, CAN PROVIDE THE AVAILABLE FAULT CURRENT AT
 THEIR POINT OF SERVICE. NEC 110.9
 PROVIDE A DEDICATED SPACE FOR THE SERVICE PANEL BOARDS.
 NEC 110. 26 (F)
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE
 GROUND. NEC 250.94
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  