| 2011-11-30 12:11:30 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. OK. |
| | |
| | 2. ORIENTATION OF NORTH APPEAR TO CONFLICT ON VARIOUS |
| | SHEETS; FOR INSTANCE, SEE U1 AND A 1A. DUE TO |
| | CONFLICTING INFORMATION IT IS UNCLEAR WHETHER THE 1 |
| | HOUR RATED WALL SHOWN ON A1A IS THE WALL FACING THE |
| | EAST PROPERTY LINE OR THE STREET TO THE WEST. NOTE THAT |
| | THE WALL WHICH (BASED ON SHEET U1) SHOULD FACE THE |
| | PROPERTY LINE HAS A WINDOW IN THE WALL; WHEN SUBMITTING |
| | PRODUCT APPROVALS ADDRESS BOTH FIRE RESISTANCE AS WELL |
| | AS IMPACT PROTECTION FOR THE DRIVE THROUGH WINDOW. SEE |
| | ALSO FBC TABLE 704.8 (OPENINGS IN RATED WALLS). REVISE |
| | PLAN TO SHOW COMPLIANCE WITH FBC TABLE 602 AND TABLE |
| | 704.8. |
| | |
| | 2ND REVIEW, NORTH ORIENTATION CORRECTED BUT INFORMATION |
| | REQUESTED REGARDING WALL WITHIN 20' OF THE PROPERTY |
| | LINE NOT PROVIDED. THE WALL REFERENCING FBC TABLE 602 |
| | FACES THE STREET (WEST SIDE). THE EAST SIDE (LEFT SIDE |
| | OF THE PLAN AS NORTH NOW POINTS DOWN) IS TO SHOW |
| | COMPLIANCE WITH FBC TABLE 602, 704.8. |
| | |
| | 3. OK |
| | |
| | 4. ORIENTATION OF STRUCTURE IS NOT CLEAR, SEE OTHER |
| | COMMENTS, BUT IT APPEARS THAT THE ONLY EXIT IS COVERED |
| | BY THE SAME STRUCTURE AS THE PROPOSED FUEL CANOPY. IS |
| | THIS CORRECT AND DESIGNER'S INTENT? |
| | |
| | 2ND REVIEW, NO RESPONSE LETTER PROVIDED. |
| | |
| | 5. OK. |
| | |
| | 6. A LIFE SAFETY PLAN WAS REQUESTED IN FIRST REVIEW, |
| | BUT NOT PROVIDED. HOWEVER, PLAN WAS REVISED TO INCLUDE |
| | BREAKDOWN BY AREA AND OCCUPANT LOAD. AS THE OCCUPANT |
| | LOAD EXCEEDS 49, TWO EXITS REQUIRED FBC TABLE 1015.1. |
| | |
| | 7. BASED ON BUILDING AREA SHOWN ON SHEET 1, 2500 SF, |
| | AND FBC TABLE 1004.1.1 (30 SF PER OCCUPANT FOR |
| | MERCANTILE, GROSS FLOOR AREA), IT APPEARS THAT TWO |
| | EXITS MAY BE REQUIRED, FBC 1015. PROVIDE CALCULATIONS |
| | FOR OCCUPANT LOAD AND EXITING RATIONALE. |
| | |
| | 2ND REVIEW, DESIGNER HAS STATED THAT OCCUPANT LOAD IS |
| | 84 (A1B), BUT ONLY ONE EXIT IS PROVIDED. PLEASE |
| | ADDRESS. |
| | |
| | 8. OK. |
| | |
| | 9. OK. |
| | |
| | 10. PROVIDE PRODUCT APPROVALS FOR ALL COMPONENTS AND |
| | CLADDING, FBC1609 (DOORS, STOREFRONT, DRIVE THROUGH |
| | WINDOW, BULLET PROOF/IMPACT WINDOWS, ROOF, ROOF STANDS, |
| | ETC.). |
| | |
| | 2ND REVIEW, NOT ADDRESSED. PRODUCT APPROVALS TO BE |
| | REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL. |
| | |
| | 11. PROVIDE DETAILS FOR THE FIRE RATED WALLS AND OTHER |
| | ELEMENTS REQUIRED FOR BUILDING TYPE VA, FBC 703. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. |
| | |
| | 12. IMPACT FEE ASSESSMENT REQUIRED, PLEASE CONTACT PALM |
| | BEACH COUNTY, 561 233 5025. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. |
| | |
| | 13. PROVIDE A SOILS INVESTIGATION REPORT, FBC 1802.4. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. |
| | |
| | 14. (NEW COMMENT) SEE FBC 11-4.7, CURB RAMP REQUIRED |
| | WHERE ACCESSIBLE ROUTE CROSSES A CURB. |
| | |
| | ***WHEN RESUBMITTING, PLEASE INCLUDE A WRITTEN RESPONSE |
| | LETTER.*** |
| | |
| | |