2011-11-30 12:11:30****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. OK.
  
 2. ORIENTATION OF NORTH APPEAR TO CONFLICT ON VARIOUS
 SHEETS; FOR INSTANCE, SEE U1 AND A 1A. DUE TO
 CONFLICTING INFORMATION IT IS UNCLEAR WHETHER THE 1
 HOUR RATED WALL SHOWN ON A1A IS THE WALL FACING THE
 EAST PROPERTY LINE OR THE STREET TO THE WEST. NOTE THAT
 THE WALL WHICH (BASED ON SHEET U1) SHOULD FACE THE
 PROPERTY LINE HAS A WINDOW IN THE WALL; WHEN SUBMITTING
 PRODUCT APPROVALS ADDRESS BOTH FIRE RESISTANCE AS WELL
 AS IMPACT PROTECTION FOR THE DRIVE THROUGH WINDOW. SEE
 ALSO FBC TABLE 704.8 (OPENINGS IN RATED WALLS). REVISE
 PLAN TO SHOW COMPLIANCE WITH FBC TABLE 602 AND TABLE
 704.8.
  
 2ND REVIEW, NORTH ORIENTATION CORRECTED BUT INFORMATION
 REQUESTED REGARDING WALL WITHIN 20' OF THE PROPERTY
 LINE NOT PROVIDED. THE WALL REFERENCING FBC TABLE 602
 FACES THE STREET (WEST SIDE). THE EAST SIDE (LEFT SIDE
 OF THE PLAN AS NORTH NOW POINTS DOWN) IS TO SHOW
 COMPLIANCE WITH FBC TABLE 602, 704.8.
  
 3. OK
  
 4. ORIENTATION OF STRUCTURE IS NOT CLEAR, SEE OTHER
 COMMENTS, BUT IT APPEARS THAT THE ONLY EXIT IS COVERED
 BY THE SAME STRUCTURE AS THE PROPOSED FUEL CANOPY. IS
 THIS CORRECT AND DESIGNER'S INTENT?
  
 2ND REVIEW, NO RESPONSE LETTER PROVIDED.
  
 5. OK.
  
 6. A LIFE SAFETY PLAN WAS REQUESTED IN FIRST REVIEW,
 BUT NOT PROVIDED. HOWEVER, PLAN WAS REVISED TO INCLUDE
 BREAKDOWN BY AREA AND OCCUPANT LOAD. AS THE OCCUPANT
 LOAD EXCEEDS 49, TWO EXITS REQUIRED FBC TABLE 1015.1.
  
 7. BASED ON BUILDING AREA SHOWN ON SHEET 1, 2500 SF,
 AND FBC TABLE 1004.1.1 (30 SF PER OCCUPANT FOR
 MERCANTILE, GROSS FLOOR AREA), IT APPEARS THAT TWO
 EXITS MAY BE REQUIRED, FBC 1015. PROVIDE CALCULATIONS
 FOR OCCUPANT LOAD AND EXITING RATIONALE.
  
 2ND REVIEW, DESIGNER HAS STATED THAT OCCUPANT LOAD IS
 84 (A1B), BUT ONLY ONE EXIT IS PROVIDED. PLEASE
 ADDRESS.
  
 8. OK.
  
 9. OK.
  
 10. PROVIDE PRODUCT APPROVALS FOR ALL COMPONENTS AND
 CLADDING, FBC1609 (DOORS, STOREFRONT, DRIVE THROUGH
 WINDOW, BULLET PROOF/IMPACT WINDOWS, ROOF, ROOF STANDS,
 ETC.).
  
 2ND REVIEW, NOT ADDRESSED. PRODUCT APPROVALS TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 11. PROVIDE DETAILS FOR THE FIRE RATED WALLS AND OTHER
 ELEMENTS REQUIRED FOR BUILDING TYPE VA, FBC 703.
  
 2ND REVIEW, NOT ADDRESSED.
  
 12. IMPACT FEE ASSESSMENT REQUIRED, PLEASE CONTACT PALM
 BEACH COUNTY, 561 233 5025.
  
 2ND REVIEW, NOT ADDRESSED.
  
 13. PROVIDE A SOILS INVESTIGATION REPORT, FBC 1802.4.
  
 2ND REVIEW, NOT ADDRESSED.
  
 14. (NEW COMMENT) SEE FBC 11-4.7, CURB RAMP REQUIRED
 WHERE ACCESSIBLE ROUTE CROSSES A CURB.
  
 ***WHEN RESUBMITTING, PLEASE INCLUDE A WRITTEN RESPONSE
 LETTER.***
  
  