| 2011-10-14 16:07:48 | ****CORRECTIONS**** | | | 11090826 | | | | | | 1. SEPARATE PERMITS AND REVIEWS REQUIRED FOR | | | REFRIGERATION EQUIPMENT, HOOD, AND FUEL. FDEP APPROVAL | | | REQUIRED PRIOR TO SUBMITTAL FOR FUEL PERMIT. | | | | | | 2. OUTSIDE AIR DUCT REQUIRES A DAMPER, FBC | | | 13.409.AB.3.3. | | | | | | 3. SHOW CONDENSATE DISCHARGE, FBC MECHANICAL 307.2.1. | | | | | | 4. PROVIDE A DETAIL FOR THE CURB, FBC 1609. | | | | | | |
|