| 2011-10-04 13:20:20 | 1270 PALM BEACH LAKES BOULEVARD |
| | PERMIT #11090826 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | WORKING AND TESTED WET FIRE HYDRANT REQUIRED PRIOR TO |
| | CONSTRUCTION. |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| | LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL |
| | CONTRAST THE BACKGROUND. |
| | |
| | PROVIDE WEATHERPROOF NO SMOKING OR OPEN FLAME SIGNS AT |
| | EACH FUEL STATION ISLAND. |
| | |
| | COMMERCIAL COOKING EQUIPMENT AND EXHAUST HOOD REQUIRED |
| | TO BE PROTECTED BY A WET CHEMICAL SUPPRESSION SYSTEM. |
| | SEPARATE PLANS AND PERMITS NEEDED FOR HOOD AND |
| | SUPPRESSION SYSTEM. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE |
| | DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE |
| | RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF |
| | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF |
| | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE |
| | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST |
| | TO OPERATE. |
| | |
| | DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE |
| | HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE |
| | THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT |
| | TEMPERATURE REACHES 475F DEGREES AT 1 INCH BELOW THE |
| | SURFACE. |
| | |
| | PROVIDE AN 8? TALL STEEL BAFFLE OR PROVIDE 16? OF SPACE |
| | BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE |
| | ADJACENT EQUIPMENT. |
| | |
| | SHEET 1: THE CURBING LOCATED FROM THE NORTH ENTRANCE TO |
| | THE WEST ENTRANCE SHALL BE DESIGNATED AS A FIRE LANE. |
| | ALSO THE CURBING IN FRONT OF THE NEW FIRE HYDRANT SHALL |
| | BE DESIGNATED AS A FIRE LANE. THE FIRE LANE SHALL BE |
| | MARKED WITH PAINTED CURBS AND FREE-STANDING SIGNS. FIRE |
| | LANES SHALL INDICATE NO PARKING - FIRE LANE. |
| | |
| | SHEET LS-1: THE FIRE HYDRANT SHALL BE PROVIDED WITH |
| | CLEARANCES OF THE 7'-6" TO THE SIDES/FRONT AND 4'-0" TO |
| | THE REAR. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |