Plan Review Notes
Plan Review Notes For Permit 11090826
Permit Number 11090826
Review Stop E
Sequence Number 1
Notes
Date Text
2011-10-03 14:46:1311090826
 1270 PALM BEACH LAKES BLVD.
 NEW GASOLINE/ CONVENIENCE STORE
  
 SPECIFY ON THE PLANS HOW THE INTERIOR AND EXTERIOR
 LIGHTING WILL BE CONTROLLED USING MOTION SENSORS OR
 SIMILAR TECHNIQUES AS REQUIRED BY THE FLORIDA BUILDING
 CODE. AUTOMATIC LIGHTING CONTROL FBC 13-415.ABC.1.1;
 AUTOMATIC SPACE CONTROL FBC 13-415 ABC.1.2; ADDITIONAL
 CONTROLS 13-412.ABC.1.3
 VERIFY THE SERVICE EQUIPMENT IS CAPABLE TO INTERRUPT
 THE AVAILABLE FAULT CURRENT. NEC 110.9
 PROVIDE A DEDICATED SPACE FOR THE SERVICE PANEL BOARDS.
 NEC 110. 26 (F)
 A SEPARATE PERMIT AND PLAN IS REQUIRED FOR THE SITE
 LIGHTING. THE PLAN SHOULD INCLUDE PHOTO METRICS, AN
 ELECTRIC POWER PLAN, THE DESIGN WIND LOAD WITH
 ENGINEERING FOR THE LIGHT POLES, FIXTURES AND FOOTINGS.
 NEC 215-5
 GENERAL PURPOSE RECEPTACLES LOCATED WITHIN 6 FEET OF
 SINKS MUST BE GFCI PROTECTED. NEC 210.8 (B)
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE
 GROUND. NEC 250.94
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  