2011-10-14 13:27:32****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLANS APPEAR TO INCLUDE INCORRECT ADDRESS, CONFLICTS
 WITH APPLICATION, PLEASE CORRELATE.
  
 2. ORIENTATION OF NORTH APPEAR TO CONFLICT ON VARIOUS
 SHEETS; FOR INSTANCE, SEE U1 AND A 1A. DUE TO
 CONFLICTING INFORMATION IT IS UNCLEAR WHETHER THE 1
 HOUR RATED WALL SHOWN ON A1A IS THE WALL FACING THE
 EAST PROPERTY LINE OR THE STREET TO THE WEST. NOTE THAT
 THE WALL WHICH (BASED ON SHEET U1) SHOULD FACE THE
 PROPERTY LINE HAS A WINDOW IN THE WALL; WHEN SUBMITTING
 PRODUCT APPROVALS ADDRESS BOTH FIRE RESISTANCE AS WELL
 AS IMPACT PROTECTION FOR THE DRIVE THROUGH WINDOW. SEE
 ALSO FBC TABLE 704.8 (OPENINGS IN RATED WALLS). REVISE
 PLAN TO SHOW COMPLIANCE WITH FBC TABLE 602 AND TABLE
 704.8.
  
 3. THERE APPEARS TO BE A CATCH BASIN IN THE ACCESSIBLE
 ROUTE, SEE GR1, SEE FBC 11 4.5.4, GRATINGS AND REVISE
 PLAN TO SHOW COMPLIANCE.
  
 4. ORIENTATION OF STRUCTURE IS NOT CLEAR, SEE OTHER
 COMMENTS, BUT IT APPEARS THAT THE ONLY EXIT IS COVERED
 BY THE SAME STRUCTURE AS THE PROPOSED FUEL CANOPY. IS
 THIS CORRECT AND DESIGNER'S INTENT?
  
 5. IT APPEARS THAT THE PROPOSED FUEL CANOPY COVERS HALF
 OF THE ACCESSIBLE PARKING SPACE. PROVIDE MORE
 INFORMATION REGARDING THE STRUCTURE AND HOW IT WILL
 AFFECT THE ACCESSIBLE ROUTE AND EXIT AS IT IS NOT CLEAR
 WHERE STRUCTURAL SUPPORTS WILL BE. SEE ALSO FBC 11
 4.6.5, VERTICAL CLEARANCE.
  
 6. PROVIDE A LIFE SAFETY PLAN WHICH INCLUDES THE
 FOLLOWING INFORMATION:
  
 OCCUPANCY CLASSIFICATION; THIS SHOULD BE EITHER ONE
 OCCUPANCY OR MIXED OCCUPANCY, AND IF MIXED OCCUPANCY,
 PLAN SHOULD DESIGNATE EACH OCCUPANCY WITH SQUARE FOOT
 AREA OF EACH. ALSO REVISE A1B WHICH SHOWS OCCUPANCY AS
 B M. IT APPEARS THAT THE PLAN INCLUDES MERCANTILE,
 BUSINESS, AND STORAGE; NOTE AREAS WITH OCCUPANT LOAD
 CALCULATIONS.
  
 OCCUPANT LOAD BASED ON SQUARE FOOT AREA AND USE, SEE
 FBC TABLE 1004.1.1.
  
 TRAVEL DISTANCES, INCLUDING COMMON PATH OF TRAVEL
  
 IN MAKING THE DECISION AS TO WHO WILL PREPARE THE LIFE
 SAFETY PLAN AND ADDRESS OTHER EXITING CONCERNS, PLEASE
 SEE:
  
 HTTP://WWW.FLENG.ORG/LEGAFF.CFM?PICKED=81 FOR A LINK TO
 A BUILDING OFFICIALS GUIDE TO DESIGN PROFESSIONAL
 PRACTICE OF ARCHITECTS & ENGINEERS IN FLORIDA, OR SEE
 THE FOLLOWING FOR A DIRECT LINK TO THE DOCUMENT:
  
 HTTP://WWW.FLENG.ORG/IMAGES/FILES/03012011%20PUBLISH%20
 -%20BUILDING_OFFICIALS_GUIDE_TO_DESIGN_PROFESSIONAL_PRA
 CTICE%20-.PDF
  
 7. BASED ON BUILDING AREA SHOWN ON SHEET 1, 2500 SF,
 AND FBC TABLE 1004.1.1 (30 SF PER OCCUPANT FOR
 MERCANTILE, GROSS FLOOR AREA), IT APPEARS THAT TWO
 EXITS MAY BE REQUIRED, FBC 1015. PROVIDE CALCULATIONS
 FOR OCCUPANT LOAD AND EXITING RATIONALE.
  
 8. DOOR 1 IS DEPICTED IN THE PLAN AS A SLIDING DOOR,
 SHEET A16 SCHEDULE CALLS FOR A SWING DOOR. SEE FBC
 1008.3.3 REGARDING REQUIREMENTS FOR SLIDING DOOR,
 REVISE PLAN TO SHOW COMPLIANCE AND SUBMIT PRODUCT
 APPROVAL IS DESIGN INTENT IS A SLIDING DOOR IN THIS
 LOCATION.
  
 9. DOOR 7 IS LOCATED IN A FIRE PARTITION, SEE FBC706.7,
 SPECIFY FIRE RATING FOR DOOR.
  
 10. PROVIDE PRODUCT APPROVALS FOR ALL COMPONENTS AND
 CLADDING, FBC1609 (DOORS, STOREFRONT, DRIVE THROUGH
 WINDOW, BULLET PROOF/IMPACT WINDOWS, ROOF, ROOF STANDS,
 ETC.).
  
 11. PROVIDE DETAILS FOR THE FIRE RATED WALLS AND OTHER
 ELEMENTS REQUIRED FOR BUILDING TYPE VA, FBC 703.
  
 12. IMPACT FEE ASSESSMENT REQUIRED, PLEASE CONTACT PALM
 BEACH COUNTY, 561 233 5025.
  
 13. PROVIDE A SOILS INVESTIGATION REPORT, FBC 1802.4.
  
  