| Notes |
| Date |
Text |
| 2011-09-30 16:35:30 | REPAIRS BUILDING REVIEW CHECKLIST. | | | 2007 FBC- EXISTING BUILDING. | | | | | | 1- IRON WORK TO BE REPAIRED/REPLACED IS STRUCTURAL. IT | | | SUPPORTS THE ROOF ABOVE. NEED TO PROVIDE ENGINEER OR | | | ARCHITECT DRAWINGS AND SPECIFICATIONS TO COMPLY WITH | | | SEC. 506 OF 2007 FBC-EXISTING BUILDING. | | | | | | 2- PROVIDE 2 COMPLETE SETS SIGNED AND SEALED AS | | | REQUIRED BY CHAPTER 471 OR CHAPTER 481 FLORIDA STATUTES | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|