| Plan Review Notes For Permit 11090809 |
| Permit Number |
11090809 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-11-14 10:34:45 | MECHANICAL REVIEW APPROVED WITH PROVISO: | | | | | | 1- REVISE EQUIPMENT SIZING CALCULATIONS: | | | A) EQUIPMENT SIZING CALCULATIONS WERE DONE FOR WORST | | | CASE SCENARIO. EQUIPMENT SIZING CAN'T BE DONE FOR WORST | | | CASE. ACTUAL HOUSE DIRECTIONAL ORIENTATION NEED TO BE | | | USED FOR THE CALCULATIONS. REVISE CALCULATIONS AND | | | EQUIPMENT SIZING AS REQUIRED. SEC. N1107.AB.1. | | | | | | B) REVISE DOOR TYPE AND CEILING VENTILATION AND R VALUE | | | TO MATCH REVISED ENERGY CALCULATIONS. | | | | | | C) REVISE EQUIPMENT SPECIFICATIONS ON A/C PLAN TO | | | REFLECT REVISED CALCULATIONS. |
|