| Permit Number |
11090809 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-10-14 16:25:54 | NSR RESIDENCE (R3) PLUMBING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- PLUMBING RISER DIAGRAM ON SHEET S-4 SHOWS OUTDOOR | | | SHOWER CONNECTED TO THE SANITARY DRAINAGE. THIS IS NOT | | | ALLOWED BY CITY ORDINANCE 90-125. REVISE AS REQUIRED. | | | | | | 2- KITCHEN SINK AND DISHWASHER AREA SHOW 2" VENT TO | | | ROOF. PLANS SHOW THAT THE KITCHEN SINK IS LOCATED ON AN | | | ISLAND COUNTER. REVISE AS REQUIRED TO MATCH PLANS. SEC. | | | 106.1.1 CITY AMENDMENTS TO FBC. | | | | | | 3- REVISE PLUMBING RISER DIAGRAM TO MATCH ACTUAL LAYOUT | | | AND LOCATION OF FIXTURES AS SHOWN ON FLOOR PLANS. SEC. | | | 106.1.1 CITY AMENDMENTS TO FBC. | | | | | | 4- PER BUILDING OFFICIAL, PLUMBING RISER DIAGRAM MAY BE | | | DRAWN BY THE LICENSED PLUMBER CONTRACTOR DOING THE JOB | | | AS LONG AS HE/SHE PROVIDES THE NAME, LICENSE NUMBER AND | | | SIGN THE DIAGRAM. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|