2011-10-14 16:25:54NSR RESIDENCE (R3) PLUMBING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PLUMBING RISER DIAGRAM ON SHEET S-4 SHOWS OUTDOOR
 SHOWER CONNECTED TO THE SANITARY DRAINAGE. THIS IS NOT
 ALLOWED BY CITY ORDINANCE 90-125. REVISE AS REQUIRED.
  
 2- KITCHEN SINK AND DISHWASHER AREA SHOW 2" VENT TO
 ROOF. PLANS SHOW THAT THE KITCHEN SINK IS LOCATED ON AN
 ISLAND COUNTER. REVISE AS REQUIRED TO MATCH PLANS. SEC.
 106.1.1 CITY AMENDMENTS TO FBC.
  
 3- REVISE PLUMBING RISER DIAGRAM TO MATCH ACTUAL LAYOUT
 AND LOCATION OF FIXTURES AS SHOWN ON FLOOR PLANS. SEC.
 106.1.1 CITY AMENDMENTS TO FBC.
  
 4- PER BUILDING OFFICIAL, PLUMBING RISER DIAGRAM MAY BE
 DRAWN BY THE LICENSED PLUMBER CONTRACTOR DOING THE JOB
 AS LONG AS HE/SHE PROVIDES THE NAME, LICENSE NUMBER AND
 SIGN THE DIAGRAM.
  