| Plan Review Notes For Permit 11090790 |
| Permit Number |
11090790 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-09-30 09:33:59 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- FLAT ROOF NOA 07-1203.01 SUBMITTED WAS SUPERSEDED BY | | | MIAMI-DADE. VISIT MIAMI-DADE WEBSITE AND DOWNLOAD | | | CURRENT NOA AND RESUBMIT 2 NEW COPIES. | | | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. NEED RAS 117 CALCULATIONS TO COMPLY WITH THE | | | DESIGN PRESSURES OF SEC. R301.2.1.4.3. | | | ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO | | | TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009 | | | REVISIONS THIS BUILDING IS LOCATED ON EXPOSURE "C". | | | | | | 3- SPECIFY ROOF MEAN ROOF HEIGHT TO VERIFY COMPLIANCE | | | WITH THE DESIGN PRESSURES AS REQUIRED BY SEC. | | | R301.2.1.4.3. | | | | | | 4- VALUATION DECLARED IN THE PERMIT APPLICATION WAS | | | UPDATED AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO | | | FBC. PERMIT FEE BALANCE IS $149.02. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|