Plan Review Notes
Plan Review Notes For Permit 11090776
Permit Number 11090776
Review Stop P
Sequence Number 1
Notes
Date Text
2011-10-04 15:02:33FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1) NEITHER THE PLUMBING SUPPLY NOR THE SANITARY PLANS
 INDICATE COMPLIANCE WITH 2007/09 FBC-P TABLE 403.1 FOR
 A DRINKING FOUNTAIN.
  
 2) THE PLUMBING SUPPLY RISER PLAN INDICATES A WATER
 HEATER BUT THIS APPLIANCE IS NOT LOCATED ON THE
 ARCHITECTURAL PLANS.
 THE PLUMBING SHEET FAILS TO PROVIDE INFORMATION ON
 SAFETY DEVICES :
  
 504.4 RELIEF VALVES.
 504.6 REQUIREMENTS FOR DISCHARGE PIPING.
 504.7 REQUIRED PAN.
 504.7.1 PAN SIZE & DRAIN
 504.7.2 PAN DRAIN TERMINATION.
  
 4) THE WATER PIPE ISO. ON SHEET M-2 HAS NO PIPE SIZE.
  
 5. THE MECHANICAL AREA MAY REQUIRE SANITARY DRAIN,
 VENT, DOMESTIC WATER, ETC. FOR THE VACUUM PUMP AND
 COMPRESSOR ( VACUUM DRAINS SHALL BE CONNECTED DIRECTLY
 TO SANITARY , TRAPPED, AND VENTED NFPA 99C 2005
 5.3.3.6.3)
  
 *****NOTE*****
 THE ELECTRIC SHEET E2 DOES INDICATE A VACUUM AND
 COMPRESSOR; NO MEDICAL GAS PLANS WERE SUBMITTED. A
 MED-GAS PERMIT WILL NEED TO BE ISSUED BEFORE A FRAMING
 AND PLUMBING ROUGH TO BE CERTAIN THAT NO MED-GAS LINES
 ARE TO BE INSTALLED BELOW GRADE. MED-GAS WILL BE
 REVIEWED UNDER A SEPARATE PERMIT WITH SEPARATE PLANS
 AND FEES.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  