| Plan Review Notes For Permit 11090776 |
| Permit Number |
11090776 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-10-04 15:02:33 | FBC 2007 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1) NEITHER THE PLUMBING SUPPLY NOR THE SANITARY PLANS | | | INDICATE COMPLIANCE WITH 2007/09 FBC-P TABLE 403.1 FOR | | | A DRINKING FOUNTAIN. | | | | | | 2) THE PLUMBING SUPPLY RISER PLAN INDICATES A WATER | | | HEATER BUT THIS APPLIANCE IS NOT LOCATED ON THE | | | ARCHITECTURAL PLANS. | | | THE PLUMBING SHEET FAILS TO PROVIDE INFORMATION ON | | | SAFETY DEVICES : | | | | | | 504.4 RELIEF VALVES. | | | 504.6 REQUIREMENTS FOR DISCHARGE PIPING. | | | 504.7 REQUIRED PAN. | | | 504.7.1 PAN SIZE & DRAIN | | | 504.7.2 PAN DRAIN TERMINATION. | | | | | | 4) THE WATER PIPE ISO. ON SHEET M-2 HAS NO PIPE SIZE. | | | | | | 5. THE MECHANICAL AREA MAY REQUIRE SANITARY DRAIN, | | | VENT, DOMESTIC WATER, ETC. FOR THE VACUUM PUMP AND | | | COMPRESSOR ( VACUUM DRAINS SHALL BE CONNECTED DIRECTLY | | | TO SANITARY , TRAPPED, AND VENTED NFPA 99C 2005 | | | 5.3.3.6.3) | | | | | | *****NOTE***** | | | THE ELECTRIC SHEET E2 DOES INDICATE A VACUUM AND | | | COMPRESSOR; NO MEDICAL GAS PLANS WERE SUBMITTED. A | | | MED-GAS PERMIT WILL NEED TO BE ISSUED BEFORE A FRAMING | | | AND PLUMBING ROUGH TO BE CERTAIN THAT NO MED-GAS LINES | | | ARE TO BE INSTALLED BELOW GRADE. MED-GAS WILL BE | | | REVIEWED UNDER A SEPARATE PERMIT WITH SEPARATE PLANS | | | AND FEES. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | | | | |
|