Plan Review Notes
Plan Review Notes For Permit 11090776
Permit Number 11090776
Review Stop E
Sequence Number 1
Notes
Date Text
2011-10-05 13:41:29SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 FBC EXISTING BUILDING 711.1
  
 WIRING METHODS IN THE X-RAY AND OPERATING ROOMS (
 PATIENT CARE AREAS) MUST USE A METAL RACEWAY WITH AN
 INSULATED GROUNDING CONDUCTOR OR LISTED CABLE WHICH
 PROVIDES AN EFFECTIVE GROUND FAULT CURRENT PATH. NEC
 517.13(A) AND (B)
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  