| Notes |
| Date |
Text |
| 2011-10-05 13:41:29 | SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE | | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES | | | AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL | | | FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3, | | | FBC EXISTING BUILDING 711.1 | | | | | | WIRING METHODS IN THE X-RAY AND OPERATING ROOMS ( | | | PATIENT CARE AREAS) MUST USE A METAL RACEWAY WITH AN | | | INSULATED GROUNDING CONDUCTOR OR LISTED CABLE WHICH | | | PROVIDES AN EFFECTIVE GROUND FAULT CURRENT PATH. NEC | | | 517.13(A) AND (B) | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|