2011-10-03 16:37:09BUILDING PLAN REVIEW
 PERMIT: 11090776
 ADD: 2260 PALM BEACH LAKES # 201
 CONT: LTL BUILDERS, INC
 TEL: (561)628-9753
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) OPERATING ROOM # 1, THE LAB AND LUNCH ROOM DOORS
 NEED TO COMPLY WITH:
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 2007 EXISTING BUILDING CODE: 706.1
 GENERAL. A BUILDING, FACILITY, OR ELEMENT THAT IS
 ALTERED SHALL COMPLY WITH CHAPTER 11 OF THE FLORIDA
 BUILDING CODE, BUILDING .
 FBC-B 11-4.13.6 MANEUVERING CLEARANCES AT DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN FIGURE
 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE LEVEL AND CLEAR. 18 INCHES AT LATCH
 FOR A PULL DOOR.
  
 2) PLEASE REVIEW SECTION FBC-B 11-4.13.7 TWO DOORS IN
 SERIES. 11-4.13.7 TWO DOORS IN SERIES. THE MINIMUM
 SPACE BETWEEN TWO HINGED OR PIVOTED DOORS IN SERIES
 SHALL BE 48 INCHES (1219 MM) PLUS THE WIDTH OF ANY DOOR
 SWINGING INTO THE SPACE. DOORS IN SERIES SHALL SWING
 EITHER IN THE SAME DIRECTION OR AWAY FROM THE SPACE
 BETWEEN THE DOORS [SEE FIGURE 26(A)].
  
 3) LUNCH ROOM SINK WILL NEED TO COMPLY WITH SECTIONS:
 11-4.24.1 GENERAL. SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.24.
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34 INCHES (865 MM) ABOVE
 THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE. KNEE CLEARANCE THAT IS AT
 LEAST 27 INCHES (685 MM) HIGH, 30 INCHES (760 MM) WIDE,
 AND 19 INCHES (485 MM) DEEP SHALL BE PROVIDED
 UNDERNEATH SINKS.
 11-4.24.4 DEPTH. EACH SINK SHALL BE A MAXIMUM OF 61/2
 INCHES (165 MM) DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK (SEE FIGURE 32).
 11-4.24.6 EXPOSED PIPES AND SURFACES. HOT WATER AND
 DRAIN PIPES EXPOSED UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT AGAINST CONTACT.
 THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
 11-4.24.7 FAUCETS. FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS ARE ACCEPTABLE
 DESIGNS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  