2011-09-29 14:38:59COMMERCIAL BUILDING RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL (2 COPIES)
 AS REQUIRED BY DCA RULE 9N-3. ONLY THE FLORIDA PRODUCT
 APPROVAL FL479-R3 COVER SHEET WAS PROVIDED. NEED TO
 PROVIDE TECHNICAL INFORMATION SHOWING SPECIFIC APPROVED
 ASSEMBLY TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. 1609 FBC 2007 WITH 2009
 REVISIONS.
  
 2- PROVIDE RAS 117 CALCULATIONS IF THE APPROVED
 ASSEMBLY DOESN'T MEET THE CALCULATED DESIGN PRESSURES
 REQUIRED BY SEC. 1609.
  
 3- IF PRODUCT APPROVAL SUBMITTED REQUIRES SIGNED AND
 SEALED RAS 117 CALCULATIONS, THEN SIGNED AND SEALED
 CALCULATIONS ARE REQUIRED. COORDINATE WITH ITEM #2
 ABOVE.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
  
 ***NOTE: FOR YOUR INFORMATION: A) ROOF EQUIPMENT
 REMOVAL REQUIRES SEPARATE PERMIT. B) ANY RETROFIT ROOF
 DRAINS REQUIRE PLUMBING REVIEW.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712