| 2011-10-31 09:10:19 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | (REVISED 11/1 AFTER ARCHITECT'S EMAIL 10/31, REQUESTED |
| | MISSING INFORMATION FROM CONTRACTOR VIA EMAIL) |
| | |
| | 1. PER ARCHITECT - MAIN DOOR TO COMPLY WITH EXCEPTION |
| | FBC 1008.1.8.3. |
| | |
| | PLEASE PROVIDE CLARIFICATION, DOOR 2 IS SHOWN AS |
| | EXISTING WITH PANIC HARDWARE, MY UNDERSTANDING IS THAT |
| | THIS DOOR IS TO BE REPLACED. EITHER REVISE PLAN TO |
| | INCLUDE THIS DOOR AS NEW, OR CONFIRM THAT EXISTING IS |
| | TO REMAIN AND CURRENTLY HAS PANIC HARDWARE AS STATED ON |
| | THE SCHEDULE. |
| | |
| | PER FIRE, ONLY THE MAIN DOOR FALLS UNDER THE EXCEPTION, |
| | NOT DOOR #8. |
| | |
| | PLEASE PROVIDE EITHER A MIAMIDADE NOA OR A FLORIDA |
| | STATE PRODUCT APPROVAL COVER SHEET FOR THE DOOR. ONLY |
| | EVALUATION REPORT WAS SUBMITTED FOR THE DOOR, NO |
| | FLORIDA STATE PRODUCT APPROVAL NUMBER WAS PROVIDED, |
| | FAC9N-3. |
| | |
| | PROVIDE PRODUCT APPROVAL FOR THE PROPOSED DOOR(S) WHICH |
| | REQUIRE PANIC HARDWARE, FAC9N-3. |
| | |
| | 2. ADDRESSED. |
| | |
| | 3. PROVIDE A MORE ACCURATE ADDITIONAL COST FOR THE |
| | STOREFRONT SYSTEM AND DOORS. |
| | |
| | $4000 IS NOT A REASONABLE VALUE FOR THE IMPACT |
| | STOREFRONT SYSTEM AND THREE SETS OF IMPACT DOORS. |
| | PROVIDE VALUE OF MATERIALS AND LABOR FOR INSTALLATION, |
| | FBC 108.3. |
| | |
| | ***PLEASE ADVISE IF CONTRACTOR WOULD LIKE FOR THE |
| | MECHANICAL PORTION OF THE REVISION TO BE ISSUED |
| | SEPARATELY** |
| | |