| 2011-09-29 12:31:42 | 303 EVERNIA STREET | | | PERMIT #11090673 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FIRE ALARM NOTE #2 INDICATES ALL STROBE APPLIANCES TO | | | BE AT LEAST 75 CANDELA. INDICATE THE CANDELA RATING FOR | | | THE HORN/STROBE APPLIANCES SHOWN IN SUITE 101 THROUGH | | | SUITE 104 AS THE DISTANCE FROM WALL TO WALL APPEARS TO | | | BE ROUGHLY 55 FEET. | | | | | | ELEVATOR RECALL SHALL BE INTERFACED WITH FIRE ALARM | | | SYSTEM. | | | | | | PLANS DO NOT INDICATE THE METHOD (HEAT DETECTOR/FLOW | | | SWITCH WITHOUT TIME DELAY) USED TO SHUNT TRIP POWER TO | | | THE ELEVATOR IN THE EVENT AN AUTOMATIC SPRINKLER | | | ACTIVATES IN THE ELEVATOR MACHINE ROOM. | | | | | | PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | | | VOLTAGE DROP AND BATTERY CALCULATIONS NOT SIGNED/SEALED | | | BY PROFESSIONAL ENGINEER. | | | | | | THE FIRE SPRINKLER FLOW SWITCHES AND TAMPER SWITCHES DO | | | NOT APPEAR TO BE MONITORED BY THE FIRE ALARM SYSTEM. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|