Plan Review Notes
Plan Review Notes For Permit 11090669
Permit Number 11090669
Review Stop B
Sequence Number 1
Notes
Date Text
2011-10-03 13:54:092007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SPECIFY THE DESIGN CRITERIA FOR THE NEW FOUNDATION
 ON THE PLANS INCLUDING WIND LOADS. FBC R301.1
  
 2) SHOW COMPLIANCE WITH FBC R408.1 FOR UNDER-FLOOR
 SPACE VENTILATION. SPECIFY THE LOCATIONS AND SIZES OF
 THE VENT OPENINGS.
  
 3) SHOW COMPLIANCE WITH FBC R320 FOR REQUIRED TERMITE
 PROTECTION.
  
 4) SUBMIT TWO SETS OF FOUNDATION PLANS FOR THE EXISTING
 FOUNDATION. CITY AMENDMENTS 106.1.2
  
 5) SUBMIT TWO SIGNED AND SEALED LETTERS FROM THE
 STRUCTURAL ENGINEER DETAILING AND EXPLAINING THE
 FOUNDATION REPLACEMENT PROCESS THAT WILL BE USED. ( FOR
 EXAMPLE: WILL THE ENTIRE STRUCTURE BE SUPPORTED AND
 RAISED TO ALLOW THE EXISTING FOUNDATION TO BE REMOVED
 AND REPLACED WITH THE NEW ONE? WILL IT BE DONE IN
 PHASES? ) CITY AMENDMENTS 106.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]