| Notes |
| Date |
Text |
| 2011-09-23 11:46:28 | 11090555 | | | 370 MARLBOROUGH RD | | | REWIRE EXISTING RESIDENCE | | | | | | PROVIDE AN ELECTRICAL RISER PLAN FOR THE NEW SERVICE. | | | SHOW GROUNDING, CONDUCTORS, CONDUIT SIZES AND TYPE. | | | PROVIDE FLOOR PLAN SHOWING ALL NEW AND EXISTING OUTLETS | | | INCLUDING SWITCHED OUTLETS, GFCIS, SMOKE ALARMS, CARBON | | | MONOXIDE ALARMS, AFCIS, PANELBOARD ETC. PROVIDE PANEL | | | SCHEDULE SHOWING NEW AND EXISTING CIRCUITS, 20 AMP | | | BATHROOM CIRCUITS, KITCHEN CIRCUITS ETC. VERIFY ALL | | | SAFETY CLEARANCES WILL BE PROVIDED. NEC 215.5 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | | | | |
|