Date Text
2011-09-23 11:46:2811090555
 370 MARLBOROUGH RD
 REWIRE EXISTING RESIDENCE
  
 PROVIDE AN ELECTRICAL RISER PLAN FOR THE NEW SERVICE.
 SHOW GROUNDING, CONDUCTORS, CONDUIT SIZES AND TYPE.
 PROVIDE FLOOR PLAN SHOWING ALL NEW AND EXISTING OUTLETS
 INCLUDING SWITCHED OUTLETS, GFCIS, SMOKE ALARMS, CARBON
 MONOXIDE ALARMS, AFCIS, PANELBOARD ETC. PROVIDE PANEL
 SCHEDULE SHOWING NEW AND EXISTING CIRCUITS, 20 AMP
 BATHROOM CIRCUITS, KITCHEN CIRCUITS ETC. VERIFY ALL
 SAFETY CLEARANCES WILL BE PROVIDED. NEC 215.5
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  
  